6.
Secure the paint spray gun (7) by turning the safe-
ty catch (6) with the tip as far back and up as pos-
sible.
Rectifying intake problems
Operate the valve pusher (16) 3 to 4 times to remove
any blockages or deposits from the valve.
If the problem persists: Tap the connection thread (14)
(see Fig. 10) extremely carefully several times with a
rubber mallet to loosen harder deposits.
Blow the nozzle clear (Fig. 5)
m WARNING! Always secure the paint spray gun (7)
when not in use.
1.
Turn the inserted nozzle (5) back 180 degrees
(see Fig. 4). If necessary, relieve the pressure if
the nozzle cannot be turned.
2.
Actuate the trigger lever (9) to blow the nozzle (5)
clear. Hold the paint spray gun (7) over an empty
container. As soon as a straight spray jet comes
out, the nozzle (5) is blown clear.
3.
Turn the inserted nozzle (5) forwards 180 degrees
again.
NOTE: Use an appropriate HEA filter (11) to minimise
clogging.
Work interruption
1.
Perform pressure relief.
2.
Turn the pressure control dial (3) to position 0 (off).
3.
Unplug the mains plug from the socket.
4.
Place the paint spray gun (7) in a plastic bag and
then seal it airtight.
5.
Wet the paint in the paint bucket with water so that
no skin forms on it.
12. Electrical connection
The electrical motor installed is connected and ready
for operation. The connection complies with the appli-
cable VDE and DIN provisions.
The customer's mains connection as well as the ex-
tension cable used must also comply with these reg-
ulations.
When working with spraying equipment and attach-
ments, and during temporary outdoor use, it is essen-
tial to connect the device via a residual current circuit
breaker with a tripping current of 30 mA or less.
34 | GB
Damaged electrical connection cable
The insulation on electrical connection cables is often
damaged.
This may have the following causes:
• Pressure points, where connection cables are
passed through windows or doors.
• Kinks where the connection cable has been improp-
erly fastened or routed.
• Places where the connection cables have been cut
due to being driven over.
• Insulation damage due to being ripped out of the wall
outlet.
• Cracks due to the insulation ageing.
Such damaged electrical connection cables must not
be used and are life-threatening due to the insulation
damage.
Check the electrical connection cables for damage
regularly. Ensure that the connection cables are dis-
connected from electrical power when checking for
damage.
Electrical connection cables must comply with the ap-
plicable VDE and DIN provisions. Only use connection
cables of the same designation.
The printing of the type designation on the connection
cable is mandatory.
For single-phase AC motors, we recommend a fuse
rating of C 16A or K 16A for products with a high start-
ing current (from 3000 watts)!
Connection type Y
If it is necessary to replace the mains connection ca-
ble, this must be done by the manufacturer or their rep-
resentative to avoid safety hazards.
AC motor
• The mains voltage must be 220-240 V~.
• Extension cables up to 25 m long must have a
cross-section of 1.5 mm².
13. Cleaning and maintenance
m WARNING! RISK OF INJURY! Before carrying
out any work on the device, switch off the device,
disconnect the mains plug and perform pressure
relief!
www.scheppach.com