ATTENTION
• The LPG cylinder in the compartment below the barbecue unit, must be isolated from it by a non-combustible panel. The
compartment must comply with the requirements of EN 498.
• The ventilation requirements of EN 498 for the cylinder compartment are:
• In case of a sheet metal, or similar impenetrable, structure, ventilation openings must be made on the top and bottom the
compartment or cavity, each of which must provide a free surface of at least 200 cm2 per cylinder housed; the openings
also serve as inspection points if a rubber hose is used.
215 mm
Minimum distance from
the rear wall 55mm
Min 300 mm
Min 300 mm
MAX 1,5 mt
Min 20 mm
EN
25