Refrigerant Piping Connection
When connecting refrigerant piping, do not let substances or gases other than the speci ed
refrigerant enter the unit. The presence of other gases or substances will lower the unit' s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters.
A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
Refer to the table below for specifications on the maximum length and drop height of piping.
Pipes requirements (R32 refrigerant)
Model
09 / 12
18
Note: The pipes in all cases must be copper for refrigerant gas.
CAUTION
Mark the data plate with the Ori ce installed (for some models).
Please purchase the ttings according to the requirements in the manual strictly.
Refer the diagram when installing.
Liquid side
Indoor
Outdoor
Pipes
Max. Length
(m)
Liquid
Gas
1/4"
3/8"
25
1/4"
1/2"
30
Indoor
Drop Height
(m)
10
20
Liquid side
Outdoor
X
78
Refrigerant
Additional
preload (m)
refrigerant (g/m)
5
12
5
12
Liquid side
Indoor
X
Outdoor