– Select the sub-menu and press
to show the parameters.
– Each parameter is shown with code, description and programmed setting value.
1 - Parameter code
2 - Parameter description
3 - Present setting value
4 - Selected parameter
– To modify the setting of one parameter, select it and then press
– If the dvanced level access code has not been entered, it will not be possible to enter editing pages and a access-denied message will be shown.
– If instead, the access rights are validated, then the editing screen will be shown.
1 - Selected parameter
2 - Minimum possible setting
3 - Graph bar of the value-range
4 - New value entered
5 - Maximum possible setting
6 - Previous setting
7 - Factory default setting
– When the editing screen is displayed, the parameter setting can be modified with s and t keys. The screen shows the new setting, the maximum and
minimum values, the factory default setting and a bar graph that shows the setting range.
– Pressing simultaneously s and t, the setting is set to factory default.
– Press MENU to go back to the parameter selection. The entered value is stored.
– Press MENU again to save all the settings and to quit the setup menu. The multimeter executes a reset and goes back to normal operation.
P R METER T BLE
M01 - GENER L
P01.01
CT primary
P01.02
CT secondary
P01.03
Rated voltage
P01.04
VT usage
P01.05
VT primary
P01.06
VT secondary
P01.07
Wiring
BIL = Balanced
P01.01 - CT primary winding rated current.
P01.02 - CT secondary winding rated current. DMG200 and DMG210 are fixed at 5 only.
P01.03 - Line rated voltage. Leaving at ut, the multimeter automatically adapts bar-graph full scale.
P01.04 - Set to ON if VT are used. If set to OFF, the following two parameters will be ignored.
P01.05 - VT primary winding rated voltage.
P01.06 - VT secondary winding rated voltage.
P01.07 - Set this parameter according to the used wiring diagram. See wiring diagrams on last pages of the manual.
M02 - UTILITY
P02.01
Language
P02.02
Display contrast
P02.03
High backlight level
P02.04
Low backlight level
P02.05
Low backlight delay
P02.06
Default page return
P02.07
Default page
P02.08
Default sub-page
P02.06 - If set to OFF, the display remains always at the page where the user left it. If set to a time delay, after that time, the display page goes back to page set
in P02.07.
P02.07 - Number of the page to which the display returns automatically after time specified by P02.06 has elapsed from the last keystroke.
P02.08 - Sub-page type to which the display returns after P02.06 has elapsed.
M03 - P SSWORD
P03.01
Enable passwords
P03.02
User level password
P03.03
dvanced level password
P03.01 - If set to OFF, password management is disabled and the access to setup parameters and commands menu is allowed.
P03.02 - With P03.01 enabled, value to be specified to get user access. Refer to Password ccess section.
P03.03 - Like P03.02, but referred to advanced access.
.
UdM
V
V
V
UdM
%
%
%
sec
sec
UdM
Default
Range
5
5-10000
5
5
ut
ut / 50-500000
OFF
OFF-ON
100
50-500000
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
50
0-100
100
10-100
30
10-50
30
5-600
60
OFF / 10-600
VL-L
VL-L / VL-N ...
INST
INST / HI / LO /
VG / MD /GR PH
Default
Range
OFF
OFF-ON
1000
0-9999
2000
0-9999
G
B