TECHNIC L CH R CTERISTICS
uxiliary supply
Nominal voltage Us
Rated voltage range
Frequency
Power consumption/dissipation
Immunity time for microbreakings
Voltage inputs
Type of input
Maximum rated nominal voltage Ue
UL rating
Measuring range
Frequency range
Method of measuring
Method of connection
Current inputs
Rated current Ie
Measuring range
Type of input
Measuring method
Overload capacity
Overload peak
Burden (per phase)
RS485 Serial interface (DMG210 only)
Baud-rate
Insulation
ccuracy
Measuring conditions
Voltage (L-N)
Voltage (L-L)
Current
Frequency
ctive power
ctive energy
Reactive energy
dditional errors
Voltage
Current
Power
~
100...240V
110...250V
~
85...264V
93.5...300V
45...66Hz
DMG200: 3.5V 1.2W
DMG210: 4.5V 1.7W
≥50ms
Three phase + neutral
~
690V
phase-phase
~
400V
L-N
~
600V
phase-phase
~
347V
L-N
~
20 - 830V
L-L
~
10 - 480V
L-N
45...66Hz
True RMS value
Single-phase, two-phase, three-phase with or without
neutral or balanced three-phase system
~
5
~
0.010...6
Shunt supplied by an external current transformer
(low voltage). Max. 5
True RMS value
+20% Ie
50 for 1 second
0.6W
Programmable 1200...38400 bps
1500V~ toward current inputs
Double insulation toward supply
and voltage inputs.
temperature 23°C ±2°C
~
voltage
L-N 50...480V
~
L-L 80...830V
current 0.1...1.2 In
frequency 45...66Hz
±0.2% ±0.5 digit
±0.5% ±0.5 digit
±0.5% ±0.5 digit
±0.1% ±0.5 digit
±0.1% ±0.5 digit
Class 1 (IEC/EN 62053-21)
Class 2 (IEC/EN 62053-23)
0.05%/°K
0.05%/°K
0.05%/°K
mbient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum pollution degree
Measurement category
Overvoltage category
ltitude
Climatic sequence
Mechanical shock
Vibration
Insulation
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Power frequency withstand voltage
uxiliary supply and voltage input connections
Type of terminal
Number of terminals
Conductor cross section (min... max)
Tightening torque
Current Input and RS485 (DMG210 only) connections
Type of terminal
Number of terminals
Conductor cross section (min... max)
Tightening torque
Housing
Version
Mounting
Material
Degree of protection
Weight
Certifications and compliance
Certifications obtained
UL marking
for supply/voltage inputs
for current inputs
Comply with standards
-20...+60°C
-30...+80°C
<80% (IEC/EN 60068-2-78)
2
III
3
2000m
Z/ BDM (IEC/EN 60068-2-61)
15g (IEC/EN 60068-2-27)
0,7g (IEC/EN 60068-2-6)
~
690V
9.5kV
5.2kV
Screw (fixed)
4 for voltage inputs
2 for ux supply
2
0.2...4.0mm
(24...12 WG)
0.8Nm (7lbin)
Screw (fixed)
6 for external CT connection
4 for RS485 connection
2
0.2...2.5mm
(24...12 WG)
0.44Nm (4lbin)
4 module (DIN 43880)
On 35mm DIN rail (IEC/EN 60715)
or by screw using extractible clips
Polyamide R L7035
IP40 on front,
IP20 terminals
294g (DMG200); 300g (DMG210)
cULus, GOST
Supply voltage 100...240V C or 110...250VDC
V input: 600V max
I input: 0.005...6
WG Range: 24-12 stranded or solid
Field Wiring Terminals Tightening Torque: 7-9lbin
Use 60°C/75°C copper (Cu) conductor only.
WG Range: 24-12 stranded or solid
Field Wiring Terminals Tightening Torque: 4lbin
Use 60°C/75°C copper (Cu) conductor only.
IEC/EN 61010-1, IEC/EN 61000-6-2,
IEC/EN 61000-6-3, UL508, CS C22.2 n°14
G
B
7