EVBOX Livo Manual De Instalación Y De Usuario página 34

Cable

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 123
EN
2.
Connect the network cable RJ45 plug to the CT IN
socket.
4.5.5. Only for Germany: Connect remote power control cable
The terminal blocks accept a wire gauge in the following range:
Solid wire: maximum 1.5 mm².
Stranded wire with ferrule (without plastic sleeve): maximum 1.5 mm².
The cable must be double insulated, and resistant to temperatures of up to 90 °C.
1.
Strip the wire ends of the active power control cable.
When stranded wires are used, install ferrules (without
plastic sleeves) and apply a square crimp for optimal fit
into the terminal blocks.
2.
Connect the active power control wires to the the black
terminal block (digital input 1).
3.
Connect the other end of the active power control cable to a DSO control device with normally-open (NO)
contacts.
30