3 - Press the PROG./RADIO/OPEN/START => M1 button. The M1 LSO opening limit switch will
stop M1.
4 - Press the PROG./RADIO/OPEN/START => M1 button to close. The LSC M1 limit switch will
stop M1.
At the same time the led DL1 will stop flashing signaling the exit from the learning procedure.
From this moment the safety devices or other gate commands will work normally (inversions,
stops, alarms, etc.).
5 - AT THE END OF PROGRAMMING, RESET THE DIP 2 IN OFF POSITION.
E - PEDESTRIAN OPENING
The gate must be fully closed.
1 - Turn DIP2 to ON position => the LED DL1 starts blinking quickly.
2 - Immediately, turn also DIP1 to ON position, the LED DL1 starts blinking slowly.
3 - Press the pedestrian pushbutton (COM A+/PED.), motor M1 opens
4 - When the motor M1 leaf is opened enough for the pedestrian crossing, press the pedestrian
pushbutton to stop the travel (thus defining the opening stroke of motor M1).
5 - Press the pedestrian pushbutton (COM A+/PED.), M1 closes.
6 - Turn DIP1 to OFF position.
7 - Turn DIP2 to OFF position.
F - RADIO CODES PROGRAMMING PROCEDURE FOR TOTAL OPENING
(1000 CODES MAX) - with radio module ACG8069
ATTENTION: before storing the radio codes, use DIP 13 to select which transmitters to use:
DIP 13 OFF: SUN-PRO variable code transmitters can be memorized:
SUN-PRO 2CH 2-channel - red keys and white led cod. ACG6210
SUN-PRO 4CH 4-channel - red keys and white led cod. ACG6214
DIP 13 ON (by factory): You can store transmitters with fixed code SUN:
SUN 2CH 2-channel - blue keys and white led cod. ACG6052
SUN 4CH 4-channel - blue keys and white led cod. ACG6054
SUN CLONE 2CH 2-channel - blue keys and yellow led cod. ACG6056
SUN CLONE 4CH 4-channel - blue keys and yellow led cod. ACG6058
ATTENTION: it is not possible to memorize at the same time transmitters with fixed code and
transmitters with variable code.
Programming can be done only when the gate is stationary.
1 - First set DIP 1 to ON and then DIP 2 to ON. The LED DL12 flashes red for 10 seconds.
2 - Press the TRANSMITTER button (usually channel A) within the allotted 10 seconds. If the
remote is memorized properly LED DL12 blinks green and a buzzer tone confirms the correct
memorization. The 10 seconds for programming the codes are automatically renewed, with
LED DL12 which flashes red, in order to store the next transmitter.
3 - To finish programming, wait 10 seconds, or press the PROG button briefly. LED DL12 stops
flashing.
4 - Re-set DIP 1 to OFF and DIP 2 to OFF.
5 - End of procedure.
REMOTE PROGRAMMING NEW REMOTE CONTROLS DEDICATED TO TOTAL OPENING
1 - Press the button on the valid remote control dedicated to fully opening the gate 3 times in
rapid succession. The buzzer will sound once for 1 second and the flasher will flash for 4
seconds to signal the activation of the procedure.
2 - Immediately then press the same button once on the new remote control(s) you want
to register. The buzzer will sound 1 time to confirm the registration of each new remote
control. Wait 4 seconds for the procedure to exit. The flasher will turn off.
If you do not want to use this function, set DIP 3 to ON to deactivate it.
ALL RADIO CODES FOR TOTAL OPENING CANCELLATION PROCEDURE
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - LED DL12 flashes red for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two
green flashes of LED DL12 and 2 tones of the buzzer.
4 - LED DL12 flashes red again for 10 seonds and you can add new codes as shown above.
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
6 - End of procedure.
RADIO CODES MEMORY FULL INDICATOR (FOR TOTAL OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED DL12
blinks red for 10 seconds enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
4 - End of procedure.
G - RADIO CODES PROGRAMMING PROCEDURE FOR PEDESTRIAN
OPENING
(1000 CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. DL12 flashes green for 10 seconds.
2 - Press the transmitter button (usually channel B) within the allotted 10 seconds. If the
transmitter is properly memorized LED DL12 blinks red and the buzzer emits a tone. The
10 seconds are automatically renewed (DL12 flashes green) in order to memorize next
transmitter.
3 - To finish programming wait 10 seconds, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
REMOTE PROGRAMMING NEW REMOTE CONTROLS DEDICATED TO PEDESTRIAN OPENING
1 - Press the button on the valid remote control dedicated to pedestrian opening of the gate
3 times in rapid succession. The buzzer will sound 2 times for 1 second and the flasher will
flash for 4 seconds to signal the activation of the procedure.
2 - Immediately then press the same button once on the new remote control(s) you want
to register. The buzzer will sound 1 time to confirm the registration of each new remote
control. Wait 4 seconds for the procedure to exit. The flasher will turn off.
If you do not want to use this function, set DIP 3 to ON to deactivate it.
ALL RADIO CODES FOR PEDESTRIAN OPENING CANCELLATION PROCEDURE
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 seconds.
2 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two red
flashes of LED DL12 and two tones of the buzzer.
3 - The red LED DL1 remains active and you can add new codes as shown above.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
RADIO CODES MEMORY FULL INDICATOR (FOR PEDESTRIAN OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
seconds enabling possible cancellation of codes.
3 - Set DIP 1 to OFF and DIP 3 to OFF.
4 - End of procedure.
H - PROGRAMMING RADIO CODES FOR R-AUX RELAY
(1000 CODES MAX) - with radio module ACG8069
* Remote control management can be enabled only by the RIB GATE app.
R-AUX normally works as a courtesy light for 3 minutes.
Through the RIB GATE app it is possible to configure the operation of this relay as desired.
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 seconds.
2 - Press the transmitter button (usually channel C) within the allotted 10 seconds. If the
transmitter is properly memorized LED DL12 blinks green and the buzzer emits a tone. The
10 seconds are automatically renewed (DL12 flashes orange) in order to memorize next
transmitter.
3 - To finish programming wait 10 seconds, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1, 2 and 3 to OFF.
5 - End of procedure.
REMOTE PROGRAMMING NEW REMOTE CONTROLS DEDICATED TO THE R-AUX RELAY
1 - Press the button on the valid remote control dedicated to pedestrian opening of the gate
3 times in rapid succession. The buzzer will sound 3 times for 1 second and the flasher will
flash for 4 seconds to signal the activation of the procedure.
2 - Immediately then press the same button once on the new remote control(s) you want
to register. The buzzer will sound 1 time to confirm the registration of each new remote
control. Wait 4 seconds for the procedure to exit. The flasher will turn off.
If you do not want to use this function, set DIP 3 to ON to deactivate it.
RADIO CODES CANCELLATION PROCEDURE (FOR R-AUX RELAY)
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 seconds.