FLOATING ACTUATOR
BLACK
WHITE
BROWN
3
2
4
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
USE CLASS II 24V TRANSFORMER FOR MVN643.
Fig. 11. MVN613 or MVN643 with 2-Position Control.
FLOATING ACTUATOR
BLACK
WHITE
BROWN
3
2
4
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
USE CLASS II 24V TRANSFORMER.
Fig. 12. MVN643 with Two Position SPST Control.
PROPORTIONAL/MODULATING: 4-20mA CONTROLLER OUTPUT WITH
500Ω SERIES RESISTOR
PROPORTIONAL ACTUATOR
DIP SWITCH POSITION
1
2
MODE
OFF
OFF
2-10V
OFF
ON
0-10V
ON
OFF
10-2V
ON
ON
10-0V
RED
BLACK
TO OTHER
ACTUATORS
WHITE
500 OHMS,
1/2 W
MINIMUM
+
2
1
3
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER.
2
Fig. 13. MVN713 with 4-20mA Control.
1
24 VAC
2
FLOATING
CONTROLLER
M33138C
1
2
24 VAC
SPST
M33557B
1
2
24 VAC
+
–
4-20mA
CONTROLLER
M33141B
VBN CONTROL BALL VALVES AND ACTUATORS
PROPORTIONAL/MODULATING: 0(2)...10 VDC OR 10...0(2) VDC CONTROLLER OUTPUT
PROPORTIONAL ACTUATOR
DIP SWITCH POSITION
1
2
MODE
OFF
OFF
2-10V
OFF
ON
0-10V
ON
OFF
10-2V
ON
ON
10-0V
+
2
1
3
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
Fig. 14. MVN713 with 0 (2)-10 VDC Control.
VALVES WITH FAIL-SAFE ACTUATORS
1
24 VAC
2
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
1
SPST
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 15. MS8105 with On/Off Control.
5
2
RED
BLACK
24 VAC
WHITE
+
–
0 (2)-10 VDC
CONTROLLER
1
SPST
3
2
ACTUATOR
1
V
2
2
ACTUATOR
62-2025EFS—04
1
M33140A
V
M34973
M34974