Powering Up The Flame Detector; Testing The Flame Detector - Dräger Flame 2000 Instrucciones De Uso

Ocultar thumbs Ver también para Flame 2000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 76
Possible heated optics settings
The heated mode can be set to one of the following:
OFF: Detector window is not heated
ON: Detector window is continuously heated
Automatic (default):
You can define the start temperature below which the detector
window is heated. The default is 5 °C (41 °F).
The start temperature can be defined between 0 °C (32 °F) and
30 °C (86 °F).
The heating stops when the temperature is 15 °C (approx. 27 °F)
above the start temperature.
3.3.8

Powering up the flame detector

1. Power up the system.
2. Wait approximately 60 seconds for the flame detector to finish the
start-up procedure.
The startup procedure is as follows:
The status LED flashes yellow at 4 Hz.
A BIT is executed.
If the test was successful:
The status LED flashes green at 1 Hz.
The fault relay contacts close.
The 0-20 mA output is 4 mA.
3.3.9

Testing the flame detector

1. Disconnect or disable external devices, such as automatic
extinguishing systems.
2. Make sure that the status LED flashes green.
3. Perform one of the following tests:
Manual BIT (Dräger Flame 2000/2500/2700 only, see
page 15)
Test using the corresponding Dräger flame simulator (see
page 16)
4. Connect or enable external devices, such as automatic
extinguishing systems.
Manual BIT (Dräger Flame 2000/2500/2700)
NOTICE
If the functions alarm BIT and/or auxiliary BIT are set to YES, alarm
relay, auxiliary relay, and 0-20 mA output are activated during a
manual BIT.
► Disconnect automatic extinguishing systems or any external
devices that may be activated during the test so that no fire
extinguishing measures are initiated.
en
Use
15

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Flame 2500Flame 2570Flame 2700

Tabla de contenido