Noise level measurements:
The noise level at 7 m is the average sound level (lpA) obtained in four
directions and 7 meters from the generator.
NOTE: The level noise may change noticeably in different environments.
Equipment regulation compliance:
Tested in accordance to EN12601:2010: safety in generators powered by
combustion engine
In accordance to guidelines 2006/42/EC Machinery safety
In accordance to guidelines 2006/95EC
In accordance to guidelines 2004/108/EC Electromagnetic compatibility
In accordance to 2000/14/EC (guideline 2005/88/EC) Sound emissions of the
exterior equipment on stage II June 2006.
Environmental correction
Power specifications indicated are with the following values:
Altitude:0m
Ambient temperature:25º
Factor "A" of environmental correction (Temperature and altitude):
Altitude
(meters)
25
0
1
500
0,93
1000
0,87
2000
0,75
3000
0,64
4000
0,54
Factor "B" of environmental correction (humidity):
Relative humidity 60 %
Relative humidity 80%
Relative humidity 90%
Relative humidity 100%
Ambient temperature (degrees Celsius)
30
35
0,98
0,96
0,91
0,89
0,85
0,82
0,73
0,71
0,62
0,6
0,52
0,5
correction factor C - 0.01
correction factor C - 0,02
correction factor C - 0,03
correction factor C - 0,04
33
Low voltage
Relative humidity:30%
40
0,93
0,90
0,87
0,84
0,80
0,78
0,69
0,66
0,58
0,56
0,48
0,46
45