Ferroli ENERGY TOP B 80 Instrucciones De Uso página 77

Ocultar thumbs Ver también para ENERGY TOP B 80:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
To connect several opposed modules
Optional kit code 042026X0 is available for connecting the water and gas manifolds in
series. The kit contains 3 flanged "U" pipes.
C
B
1
2 - 3
fig. 25 - Kit for connection of opposed modules
A
1st Module
B
2nd Module
C
3rd Module
D
4th Module
1
Gas inlet
2
System delivery
3
System return
5
Blind flanges
7
Drilled flanges
8
Seals and screws (standard)
Arrange the modules according to the layout of fig. 25.
Connect the first module to the system and gas pipes using the flanges with pipe
section and respective seals contained in the kit 042027X0.
Position the second module, making sure to align the connection flanges and the
condensate drain pipe. Fit the seals (supplied) between the flanges of the two mod-
ules.
Fit the bolts (supplied) on the flanges from inside the first module, making them
come out the flanges in the second module. Partially tighten the nuts on the bolts
from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and fit
the condensate drain pipes of the two modules (see fig. 53).
Tighten the nuts and repeat the connection operations for the "U" pipes and next
modules. Fit the blind flanges contained in the kit 042027X0 on the last module.
Safety device and separator module (optional)
The Safety Device and Separator Module for series ENERGY TOP Bmodular gener-
ators is an ISPESL certified module containing a hydraulic separator and safety, protec-
tion and control devices required by file "R" section R3A and R3B, intended for use with
series ENERGY TOP Bmodular generators .
Every ISPESL Safety Device Module comprises a cabinet of the same size and appear-
ance as the modular generators ENERGY TOP B, containing a hydraulic separator with
air valve and thermal insulation, the respective system delivery and return manifolds, a
gas manifold, and a discharge manifold for the safety valve. The safety devices required
by file "R" section R3A and R3B are fitted on the hydraulic manifolds and hydraulic sep-
arator body. Provision is also made for the probe pocket of a possible fuel shutoff valve,
to be installed in the system , on the outside of the bank of modules.
The hydraulic separator contained in the module allows the hydraulic circuit of the mod-
ules ENERGY TOP B (primary circuit) to be made independent of the hydraulic circuit of
the respective heating system (secondary circuit). The separator is sized for correct op-
eration up to 1000 kW, and the main advantages offered are:
An external circulating pump for the primary circuit is not necessary. In fact, circula-
tion in the primary circuit is ensured by the circulating pumps contained inside the
generators ENERGY TOP B.
When the secondary pump is deactivated, also the circulation in the system circuit
stops; the entire flow delivered by the circulating pumps contained inside the gener-
ators ENERGY TOP B is bypassed through the hydraulic separator.
The flow in the primary circuit can remain constant, whereas the secondary circuit
can function with a variable or intermittent flow rate.
There are no anomalous operating conditions in which the system pumps interact
with the circulating pumps in side the generators ENERGY TOP B, creating unwant-
ed head and flow-rate variations in the circuits.
Sizing of the system circulating pump can be carried out according to the needs of
just the secondary circuit.
76
EN
2
1
3
8
D
1
2
3
A
7
cod. 3541H060 - Rev. 02 - 04/2018
A
fig. 26 - Opposed configurations
A
1st Module
B
2nd Module
1
Gas inlet
2
System delivery
3
System return
4
Hydraulic separator
The safety devices and separator module must be installed directly next to the last mod-
ule ENERGY TOP B making up the modular generator. The particular symmetrical
5
shape of the module allows it to be installed on the right side and left side of the generator
bank. Some possible connection examples are given below.
C
4
2
3
fig. 27 - Configuration in line
C
3rd Module
1
Gas inlet
2
System delivery
3
System return
4
Hydraulic separator
Plumbing circuit examples
Key of examples
I
ISPESL safety devices
D
Hydraulic separator
42
DHW temperature sensor (not supplied)
72
Room thermostat (not supplied)
72b
Room thermostat (not supplied)
95
3-way valve - with spring return: at rest on DHW side (not supplied)
130
Hot water tank circulating pump (not supplied)
138
External probe (not supplied)
139
Remote control (not supplied)
298
Cascade temperature sensor (not supplied)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
SM
Delivery probe (supplied with kit FZ4)
TS
Safety thermostat (not supplied)
PZ
Zone pump (not supplied)
FZ4
Zone regulator
Parameters
Each system requires a different parametrisation. Follow the procedure for accessing the
two menus, given below; for the parameters to be modified, refer to the tables given
alongside the plumbing diagrams.
ENERGY TOP B
B
4
2
3
1
4
2
3
1
1

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Energy top b 160Energy top b 125Energy top b 250

Tabla de contenido