"Service Menu"
Press the Reset button for 10 seconds to access the card Service Menu.
Press the Heating buttons to select "tS", "In", "Hi" or "rE". tS" means Transparent Param-
eters Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. Se-
lect "tS" and press the RESET button.
The card has 29 transparent parameters also modifiable from Remote Control (Service
Menu).
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"System Type Menu"
Press the Summer/Winter button for 10 seconds to access the card System Type Menu.
The card has 21 transparent parameters.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Summer/Winter button for 10 seconds to exit the card System Type Menu.
One direct heating circuit
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
138
One direct heating circuit and one DHW circuit with pump
Check/Change parameter P02 of the "Transparent Parameters Menu" to 5.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
138
I
298
306
D
fig. 28
42
I
130
298
306
D
fig. 29
cod. 3541H060 - Rev. 02 - 04/2018
One direct heating circuit and one DHW circuit with diverter valve
Check/Change parameter P02 of the "Transparent Parameters Menu" to 6.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
Change parameter P.11 of the "System Type Menu" to 1.
138
Two direct heating circuits
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4.
Change parameter P.01 of the "System Type Menu" to 4.
72/139
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
138
A
Two mixed heating circuits and one direct heating circuit
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
72/139
For the electrical connection and the zone system settings, refer to the "FZ4 zone regu-
lator" handbook
138
B
42
I
298
95
306
D
fig. 30
72/139
I
307
298
D
fig. 31
FZ4
72/139
72/139
Zona 1
Zona 2
TS
TS
I
PZ
PZ
SM
SM
M
M
298
D
fig. 32
EN
72/139
C
72b
306
D
72/139
Zona 3
PR
E
77

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Energy top b 160Energy top b 125Energy top b 250

Tabla de contenido