Checks during operation
Turn the unit on as described in sec. 2.3.
Make sure the fuel circuit and water systems are tight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check the correct tightness and functionality of the condensate elimination system
and trap.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water
production phases.
Check proper boiler lighting by doing several tests, turning it on and off with the room
thermostat or remote control.
Using a combustion analyser connected to the boiler fume outlet, check that the
CO
content in the fumes, with the boiler operating at max. and min. output, corre-
2
sponds to that given in the technical data table for the corresponding type of gas.
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table on sec. 5.4.
Check the correct programming of the parameters and carry out any necessary cus-
tomization (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To keep the unit working properly over time, it is necessary to have qualified personnel
make an annual check that includes the following tests:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly.
The fume extraction circuit must be fully efficient.
The airtight chamber must be sealed
The air-fume end piece and ducts must be free of obstructions and leaks
The condensate evacuation system must be efficient with no leakage or obstruc-
tions.
The burner and exchanger must be clean and free of scale. When cleaning, do not
use chemical products or wire brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value.
The circulation pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.
The boiler casing, panel and aesthetic parts can be cleaned with a soft damp
A
cloth, possibly soaked in soapy water. Do not use any abrasive detergents and
solvents.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 20 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the RESET button (detail 8 - fig. 1) for 1 second or RESET on the
optional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Other faults (marked with the letter "F") cause temporary shutdowns that are automati-
cally reset as soon as the value returns within the boiler's normal working range, except
for fault F37 which is reset by turning the unit off and then on again with button 14 of
fig. 1.
Table of faults
Table. 6 - List of faults
Fault
Fault
Possible cause
code
No gas
Ignition/detection electrode fault
A01
No burner ignition
Faulty gas valve
Insufficient gas supply pressure Check the gas supply pressure
Trap blocked
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature protec-
A03
No water circulation in the sys-
tion intervention
tem
Air in the system
Fume extraction duct
Fault F07 generated 3 times in
A04
safety device intervention
the last 24 hours
Fault F15 generated for 1 hour
A05
Fan protection activated
(consecutive)
84
EN
Cure
Check the regular gas flow to the boiler
and that the air has been eliminated from
the pipes
Check the wiring of the electrode and that
it is correctly positioned and free of any
deposits
Check the gas valve and replace it if nec-
essary
Check the trap and clean it if necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and opera-
tion of the heating sensor
Check the circulating pump
Vent the system
See fault F07
See fault F15
cod. 3541H060 - Rev. 02 - 04/2018
Fault
Fault
Possible cause
code
Ionisation electrode fault
Flame unstable
No flame after ignition
Gas valve Offset fault
A06
stage (6 times in 4 min-
utes)
air/fume ducts obstructed
Trap blocked
Flue partially obstructed or
insufficient
F07
High fume temperature
Fume sensor position
Sensor damaged
F10
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Sensor damaged
F11
Return sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F12
DHW sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
F13
Fume sensor fault
EXCHANGER SAFETY THER-
MOSTAT ACTIVATED
Sensor damaged
F14
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
No 230V power supply
F15
Fan fault
Tachometric signal interrupted
Fan damaged
Faulty RESET button on
Blocked or faulty RESET button
F26
controller CENTRALINA
on controller CENTRALINA
located on gas valve
located on gas valve
Supply voltage under
F34
Electric mains trouble
170V
F35
Faulty mains frequency
Electric mains trouble
Insufficient system pressure or
circulation
Flowswitch or pressure
F37
Circulating pump not working
switch contact open
Wrong card parameter setting
Flowswitch contact
F38
Flowswitch dirty or blocked
blocked closed
Probe damaged or wiring
shorted
F39
External probe fault
Probe disconnected after acti-
vating the sliding temperature
Delivery sensor disconnected
A41
Sensor positioning
from the pipe
A42
Heating sensor fault
Sensor damaged
F42
Heating sensor fault
Sensor damaged
Sensor damaged
Cascade temperature
F50
Wiring shorted
sensor fault
Wiring disconnected
Controller CENTRALINA
Controller CENTRALINA inter-
A61
fault
nal error
No communication
Controller not connected
A62
between controller and
Valve damaged
gas valve
A63
A64
Controller CENTRALINA
Controller CENTRALINA inter-
A65
fault
nal error
F66
Fault F13 generated 3 times in
A80
Fume sensor fault
the last 24 hours
ENERGY TOP B
Cure
Check the position of the ionisation elec-
trode and replace it if necessary
Check the burner
Check the Offset adjustment at minimum
power
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Check the trap and clean it if necessary
Check the efficiency of the flue, fume
extraction ducts and outlet terminal
Check the correct positioning and opera-
tion of the fume sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
CHECK THE BOILER SHELL AND
CLEAN IT IF NECESSARY
Check the thermostat and replace it if
necessary
Check the thermostat wiring
Check the wiring or replace the sensor
Check the 3-pin connector wiring
Check the 5-pin connector wiring
Check the fan
Check the RESET button and replace the
controller CENTRALINA if necessary
Check the electrical system
Check the electrical system
Check the system water pressure or for
air in the system
Check the circulating pump
Check the card parameter and modify it if
necessary
Clean the flowswitch or replace it if nec-
essary
Check the wiring or replace the sensor
Reconnect the external probe or disable
the sliding temperature
Check the correct positioning and opera-
tion of the heating sensor
Replace the sensor
Replace the sensor
Check the wiring or replace the sensor
Check the earth connection and replace
the controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the earth connection and replace
the controller if necessary.
See fault F13