In automatic mode, the controller calculates the optimum configuration of capacitor steps
in order to reach the set cosø.
The selection criteria takes into account many variables such as: the power of each step, the
number of operations, the total time of use, the reconnection time, etc.
The controller displays the imminent connection or disconnection of the steps with the
flashing of their identification number (left). The flashing can last in cases in which the
insertion of a step is not possible due to the reconnection time (discharge time of the
capacitor).
The device initiates automatic corrections when there is an average reactive power request
(delta-kvar) higher than 50% of the smallest step, and the measured cosø is different from
the setpoint.
The PFC96evo controller provides a set of measurements displayed on the alphanumeric
display, in conjunction with the current cosø that is always displayed on the main display.
Press the
key to scroll through the measures in rotation.
After 30 seconds without pressing any buttons, the display automatically returns to the
default measurement defined by P.47.
If P.47 is set on the ROT, then the measures rotate automatically every 5 seconds.
At the bottom of the list of measures it is possible to set the setpoint of the cosø, acting on
the same value set with P.19.
Below is a table with the measurements displayed.