Parameter Table; Base Menu - ITALFARAD PFC96evo Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

 Below are listed all the programming parameters in tabular form. For each parameter are
indicated the possible setting range and factory default, as well as a brief explanation of the
function of the parameter. The description of the parameter shown on the display can in
some cases be different from what is reported in the table because of the reduced number
of characters available. The parameter code can be used however as a reference.
 Note: the parameters shown in the table with a shaded background are essential to the
operation of the system, thus they represent the minimum programming required for
operation.
COD
DESCRIPTION
P.01
CT primary
P.02
CT secondary
P.03
CT read phase
P.04
CT wiring polarity
P.05
Voltage read phase
P.06
Smallest step power
P.07
Rated installation voltage
P.08
Nominal frequency
P.09
Reconnection time
P.10
Sensitivity
P.11
Step 1 function
P.12
Step 2 function
P.13
Step 3 function
P.14
Step 4 function
P.15
Step 5 function
P.16
Step 6 function
P.17
Step 7 function
P.19
Cos-phi setpoint
P.20 Alarm messages language
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com

Parameter table

Base menu

ACC UoM
Usr
A
Usr
A
Usr
Usr
Usr
Usr
Kvar
Usr
V
Usr
Hz
Adv
sec
Usr
sec
Usr
Usr
Usr
Usr
Usr
Usr
Usr
Usr
Usr
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
DEF
RANGE
OFF
OFF / 1...10.000
5
1 / 5
L1
L1 - L2– L2
Aut
Aut - Dir - Inv
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N
L2-L3
1.00
0.10 ... 10000
400V
50 ... 50000
Aut
Aut - 50Hz - 60Hz - Var
60
1 ... 30000
60
1 ... 1000
OFF - 1...32 - ON - NOA - NCA - FAN
OFF
MAN - AUT - A01...A12
=
OFF
=
OFF
=
OFF
=
OFF
=
OFF
=
OFF
0.95 IND 0.50 Ind – 0.50 Cap
ENG
ENG - ITA - FRA - SPA - POR - DEU
E
N
47