6. Electrical work
L N
M1
M2
S
M1
M2
S
TB1
TB3
TB7
A
B
A : Power source
B : Transmission line
C : Screw on the electrical component box
D : Screw on the electrical component box
Fig. 6-1
6.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS or CPEVS or MVVS
• Cable diameter: More than 1.25 mm
• Maximum wiring length: Within 200 m
2. M-NET Remote control cables
Kind of remote control cable
Sheathed 2-core cable (unshielded) CVV
Cable diameter
0.3 to 1.25 mm
When 10 m is exceeded, use cable with the
Remarks
same specifications as 1. Wiring transmission
cables.
* Connected with simple remote controller.
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are nec-
essary.)
<Examples of Transmission Cable Wiring>
M-NET Remote Controller (Fig. 6-2)
MA Remote Controller (Fig. 6-3)
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal
block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. The jumper connector CN41 on the control panel does not change.
Connect shield ground of the indoor units transmission line to the shield (S) terminal of (TB3) and also connect (S) terminal to screw C or D using attached lead wire.
f.
Connect shield ground of the line between outdoor units and the central control system transmission line to the shield (S) terminal of (TB7).
g. Set the address setting switch as follows.
Unit
Range
IC (Main)
01 to 50
IC (Sub)
01 to 50
Outdoor Unit
51 to 100
M-NET R/C (Main)
101 to 150
M-NET R/C (Sub)
151 to 200
MA R/C
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
i.
When connecting a PWFY unit
• Do not perform the group settings for the PWFY unit and the indoor units.
• The PWFY unit and a Lossnay unit cannot be set to operate at the same time.
• Use a WMA remote controller for the PWFY unit.
For details, refer to the installation manual for the PWFY unit.
<Permissible Lengths>
1 M-NET Remote controller
• Max length via outdoor units:
L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7
• Max transmission cable length: L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7
• Remote controller cable length: ℓ1, ℓ2, ℓ2+ℓ3, ℓ4
If the length exceeds 10 m, use a 1.25 mm2 shielded wire. The length of this section (L8) should be included in the calculation of the
maximum length and overall length.
2 MA Remote controller
• Max length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7
• Max transmission cable length (M-NET cable): L1 and L3+L4 and L6 and L2+L6 and L7
• Remote controller cable length: m1 and m1+m2 +m3 and m1+m2+m3+m4
10
C
D
2
2
(0.75 to 1.25 mm
2
)*
Use the most recent address within the same group of indoor units
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must
be in sequence with the IC (Main)
Use the most recent address of all the indoor units plus 50
* The address automatically becomes "100" if it is set as "01 - 50".
Set at an IC (Main) address within the same group plus 100
Set at an IC (Main) address within the same group plus 150
–
Unnecessary address setting (Necessary main/sub setting)
10 m (0.5 to 1.25 mm2)
6.2. Control box and connecting position of wiring
(Fig. 6-1)
1. Connect the indoor unit transmission line to transmission terminal block (TB3), or
connect the wiring between outdoor units or the wiring with the centralized control
system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmission
line to the screw (C or D) and connect shield ground of the line between outdoor
units and the central control system transmission line to the shield (S) terminal of
the centralized control terminal block (TB7) shield (S) terminal. In addition, in the
case of outdoor units whose power supply connector CN41 has been replaced
by CN40, the shield terminal (S) of terminal block (TB7) of the centralized control
system should also be connected to the screw C or D using attached lead wire.
2. Conduit mounting plates (ø27) are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
3. MA Remote control cables
Kind of remote control cable
Cable diameter
Remarks
* Connected with simple remote controller.
2 Wiring examples
• Controller name, symbol and allowable number of controllers.
Name
Outdoor unit controller
Indoor unit controller
Remote controller
Setting Method
500 m (1.25 mm2 or more)
200 m (1.25 mm2 or more)
500 m (1.25 mm2 or more)
200 m (1.25 mm2 or more)
200 m (0.3 to 1.25 mm2)
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
2
(0.75 to 1.25 mm
Within 200 m
Symbol
Allowable number of controllers
OC
–
PUMY-P100
1 to 8 units per 1 OC
PUMY-P125
1 to 10 units per 1 OC
PUMY-P140
1 to 12 units per 1 OC
IC
RC
Maximum of 12 controllers
(M-NET)
for 1 OC
RC
MA
Maximum of 2 per group
2
)*