3.4 GAS TRAIN,
(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
GAS TRAIN
TYPE
MBC 65 DLE
3970570
MBDLE 405 B01
3970546
MBDLE 405 B01
3970547
MBDLE 407 B01
3970544
MBDLE 407 B01
3970548
MBDLE 410 B01
3970549
MBDLE 412 B01
3970550
3.5
GAS TRAIN ELECTRICITY SUPPLY
The gas train's power cables can be fed to the right or
left of the burner, as illustrated in figure 6.
Depending on the entry point, the cable clamp with
pressure test point (1) and simple cable clamp (2) may
need swapping over.
Consequently, you must make sure:
the cable clamp (1) is positioned correctly;
the tube is positioned correctly so that there are no
restrictions likely to impede air flowing to the pres-
sure switch.
WARNING
If necessary, cut the tube to the right size.
3.6 GAS FEEDING LINE
1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
3080
MATCHED
BURNER
CODE
BS1
BS1
BS2
BS2
BS3 - BS4
BS3 - BS4
BS3 - BS4
1
CONNECTIONS
INLET
OUTLET
Rp 1 / 2
Flange 1
Rp 1 / 2
Flange 1
Rp 3 / 4
Flange 2
Rp 3 / 4
Flange 2
Rp 3 / 4
Flange 3
Rp 1 1 / 4
Flange 3
Rp 1 1 / 4
Flange 3
1
2
2
3
M1
4
5
D5209
MBC 65 DLE
6
7
GB
USE
Natural gas and LPG
Natural gas and LPG
Natural gas and LPG
Natural gas and LPG
Natural gas ≤ 150kW and LPG
Natural gas and LPG
Natural gas
D7113
6
7
8
8
7
D7279
Fig. 6
2
1
Fig. 7
M2