Compressor Does Not Run (Battery Connection) - Dometic GROUP WAECO CoolMatic CD50 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 68
CD50, CRD50
Interior temperature too low in control level "1"
Fault
Compressor runs con-
stantly
Compressor runs for a
long time

Compressor does not run (battery connection)

Fault
U
= 0 V
KL
≤ U
U
KL
EIN
Start attempt with
≤ U
U
KL
OFF
Start attempt with
≥ U
U
KL
ON
Electric circuit between
the pins in the compres-
sor interrupted
U
Voltage between the positive and negative terminals of the electronics
KL
U
Cut-in voltage of the electronics
ON
U
Cut-off voltage of the electronics
OFF
EN
Possible cause
Faulty thermostat
Large quantities have been frozen in
the freezer compartment
Possible cause
There is an interruption in the connec-
tion between the battery and
the – electronics
Main switch faulty (if installed)
Additional supply line fuse has blown
(if installed)
Battery voltage is too low
Loose cables
Poor contact (corrosion)
Battery capacity too low
Cable cross section too small
Ambient temperature too high
Insufficient ventilation and/or air sup-
ply
Condenser is dirty
Defective compressor
Troubleshooting
Remedy
Change the thermostat
Remedy
Establish a connection
Replace the main switch
Replace the supply line
fuse
Charge the battery
Establish a connection
Replace the battery
Replace the cable
(fig. 9, page 6)
Move the refrigerator to
another location
Clean the condenser
Replace the compressor
45

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Waeco coolmatic crd50

Tabla de contenido