PORO OPTION – ELECTRO–PNEUMATIC
POWER OUTAGE RESTART OPTION
For customers that have interruptions in their incoming power supply
to the compressor and must maintain an uninterrupted supply of
compressed air, the Power Outage Restart Option allows a
compressor to restart automatically 10 seconds (adjustable) after
incoming power is restored.

FUNCTION TEST

To test the operation of the Power Outage Restart Option:
1. Slowly open the main isolation valve.
2. Start the compressor.
3 The compressor will load automatically if there is sufficient demand
for air. Allow the compressor to load.
4. Open the main disconnect to remove power from the compressor.
5. Close the main disconnect to reapply power to the compressor. The
horn will sound for ten seconds; then the compressor will start
automatically.
http:/air.ingersollrand.com
UP6 15, UP6 20, UP6 25, UP6 30