External Combustion Air Connection; Installing The Stove; Assembly Sequence; Installation De Distribution D'eau - Olsberg Tolima Aqua Compact Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

External combustion air connection

In order to feed the combustion air to the stove ex-
ternally via a pipe instead of from the room in which it
is installed, it is possible to screw a ∅125 mm com-
bustion air pipe to the back of the stove, at the bot-
tom. If the combustion air pipe installed is longer than
3m, calculations will have to be carried out to verify
an adequate supply of combustion air. Use the Ols-
berg – combustion air pipes with sealing lip.

Installing the stove

The floor on which the stove is installed must be
even and horizontal. The stove may only be installed
on an adequate load-bearing floor. The stove can be
stood on a metal floor sheet or glass sheet to protect
the flooring. If the flooring or carpet is inflammable, a
stable and non-combustible spark protection plate
must be used. This must extend 50 cm to the front
and 30 cm to each side beyond the edge of the com-
bustion chamber opening.

Assembly sequence

The Ø 150 stovepipe connection can be installed
at the top or rear.
The stove is supplied ready for connection from
above. If you wish to connect it at the rear, the
following steps must be carried out to make the
necessary modifications:
Erase the cover on the back panel
-
Unscrew the cover at the back
-
Unscrew the sealing cap at the back. Use a
-
screwdriver to secure the screws through the
connection pipe from turning too.
Unscrew the connection pipe through the rear
-
hole.
After
successfully
-
cap/connection pipe close off the hole in the top
cover with the enclosed insertable cap.
Decide where the stove is to be installed. There
must be no objects made of combustible materi-
als within a distance of 80 cm of the stove's ra-
diation area, measured from the combustion
chamber's inspection glass, nor may any be
placed within this area subsequently.
Minimum distance from combustible or load-
bearing walls: Lateral 10 cm and rear: 12 cm
Install the pipe lining (provided on site) in the
chimney.The connection height can be individual-
ly specified for a top stovepipe connection, how-
ever should not exceed 1.5 m from the connector
sleeve. For the rear stovepipe connection heights
please refer the "Technical Data" table. No com-
bustible material is permitted within a radius of
20cm around the stove pipe.
Place the stovepipe (provided on site) on the
Ø160/Ø150mm transition piece of the stove.
Push the stove onto its planned position and
orient it so that the stovepipe fits into the pipe lin-
ing.
changing
the
sealing
The stovepipe connections must be airtight. The
stovepipe must not protrude into the chimney.

Water Installation

The respective locally-applicable regulations and
rules must be observed.
The installation of water connections and all elec-
trical work must be completed by certified spe-
cialists.
We recommend using the following Olsberg
components for connecting the respective items
to the heating and/or industrial water system:
- Installation unit
- Temperature difference controller TDC1
Please follow the separate assembly and opera-
tion instructions for these Olsberg components.
According to EN 12828 a safety relief valve with
a fixed response pressure setting of 2.5 bar
(Flamco, type Prescor or Caleffi, model series
311, 312, 313, 314, 513 or 514) needs to be in-
stalled on site to ensure that the operating pres-
sure will not exceed the maximum of 2.5 bar.
In addition to the requisite safety components, a
return flow booster valve must be installed, which
increases the return flow temperature to at least
55°C. (the Olsberg installation unit includes such
a valve).
The stove must never be operated without water.
The oven must never be operated without a cor-
rectly-installed and functional thermal discharge
safety device (TAS).
An outlet valve must be installed in the lower
section of the water circulation system.
To keep the stove and, in particular, the "Thermal
discharge safety device (TAS) " in fully opera-
tional condition, it is essential that the heating
system be cleaned by flushing as specified in
DIN EN 14336 (Heating systems in buildings -
Installation and commissioning of water-based
heating systems) before the stove is connected
hydraulically.
Olsberg cannot process any warranty claims un-
less provided with proof that the necessary
cleaning has been carried out.
Thermal discharge safety device
(TAS)
The TAS inlet must be connected to the building's
cold water system; water from the TAS outlet must
be allowed to flow directly into the drain.
The TAS must prevent the heater from overheating
when the heat being generated cannot be removed
by the water. Overheating would cause impermissibly
high temperatures and pressures which would result
in irreparable consequences for the wood heater. In
order to prevent this, the TAS' safety valve will open
depending on the water temperature in the wood
heater's heat exchanger (TAS sensor pocket) to al-
low cold tap water to remove the heat.
Do not add any more wood in the event of any such
malfunctioning.
11

Publicidad

Tabla de contenido
loading

Tabla de contenido