LERBAKKEN 10, 8410 RØNDE DENMARK
Terminal (31,32)
Supply:
Voltage
Power
Terminal (33,34)
Status Relay:
Voltage max.
Power max.
Current max.
Terminal CH1(11,12) CH2(13,14)
Digital output:
Voltage max.
Current max.
Terminal CH1(11,12) CH2(13,14)
Relay output:
Voltage max.
Power max.
Current max.
Installation notes:
In Class I, Division 2 installations, the subject equipment shall be mounted within a too-secured
enclosure which is capable of accepting one or more of the Class I, Division 2 wiring methods
specified in the National Electrical Code (ANSI/NFPA 70), or the Canadian Electrical Code (C22.1).
In Class I, Zone 2 installations, the subject equipment shall be mounted within a tool secured
enclosure which is capable of accepting one or more of the Class I, Zone 2 wiring methods specified in
the National Electrical Code (ANSI/NFPA 70), or the Canadian Electrical Code (C22.1). Where
installed in outdoor or potentially wet locations, the enclosure shall, at a minimum, meet the
requirements of IP54.
In Class I, Zone 2 installations, the installer shall ensure protection of supply terminals against
transient voltages exceeding 140% of the rated supply voltage.
Install in environments rated Pollution Degree 2 or better; overvoltage category I or II.
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable
ends.
For installation on the 9400 Power Rail the power must be supplied from Power Control Module Unit
9410.
Revision date:
2019-04-04
28
19.2 – 31.2 VDC
max. 3 W
Non Hazardous location: Division 2 or Zone 2 installation:
125 VAC / 110 VDC
62.5 VA / 32 W
0.5 AAC / 0.3 ADC
NPN output:
30 VDC
80 mA
Non Hazardous location:
250 VAC / 30VDC
500 VA / 60W
2 AAC / 2ADC
Version Revision
V5 R0
9202 - Versión del producto 9202-003
32 VAC / 32VDC
16 VA / 32 W
0.5 AAC / 1 ADC
Division 2 or Zone 2 installation:
32 VAC / 30VDC
64 VA / 60 W
2 AAC / 2 ADC
Prepared by:
PB
9202QF01
Page:
2/3