9202QU01
LERBAKKEN 10, 8410 RØNDE DENMARK
Installation notes 9202Axx and 9202Bxx
The module must be installed in a tool-secured enclosure suitable for the application in accordance with the
National Electrical Code (ANSI/NFPA 70) for installation in the United States, the Canadian Electrical Code for
installations in Canada, or other local codes, as applicable.
The module is galvanically isolated and does not require grounding.
Terminal 41, 42, 43, 44 are internally connected to CH1.
Terminal 51, 52, 53, 54 are internally connected to CH2.
Install in pollution degree 2, overvoltage category II in accordance with IEC 60664-1.
Use minimum 75 ºC copper conductors with wire size AWG: (26-14)
Warning: Substitution of components may impair intrinsic safety.
Avertissement : La substitution des composants peut nuire à la sécurité intrinsèque'.
There are no serviceable parts in the equipment and no component substitution is permitted
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not
separate connectors, install or remove module from Power Rail when energized and an explosive gas mixture
is present.
Avertissement : Pour éviter l'inflammation d'atmosphères explosibles, déconnectez l'alimentation avant les
opérations d'entretien. Ne montez pas ou n'enlevez pas les connecteurs quand le module est sous tension et
en présence d'un mélange de gaz. Ne montez pas ou n'enlevez pas les modules du rail d'alimentation en
présence d'un mélange de gaz.