Preparation For Use; Mounting The Tilt Mount; Attaching Either A Conduit Connection Or Cable Gland; Attaching The Flame Detector To The Tilt Mount - Dräger Flame Serie Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 74
3.3

Preparation for use

Perform the following steps to prepare and install the flame detector.
The installation sequence might vary according to the physical
structure of the site.
1. Install the flame detector:
Mount the tilt mount (see chapter 3.3.1 on page 13).
Attach a conduit connection or cable gland to the flame
detector (see chapter 3.3.2 on page 13).
Attach the flame detector to the tilt mount (see chapter 3.3.3
on page 13).
Wire the flame detector (see chapter 3.3.4 on page 13).
Mount the weather cover (see chapter 3.3.5 on page 14).
Orient the flame detector (see chapter 3.3.6 on page 14).
2. If required, adapt the configuration of the flame detector (see
chapter 3.3.7 on page 14).
3. Power up the flame detector (see chapter 3.3.8 on page 16).
4. Test the flame detector (see chapter 3.3.9 on page 16).
3.3.1

Mounting the tilt mount

► Illustration on the fold-out page (Figure C)
1. Place the tilt mount in its designated location.
2. Secure the tilt mount to the wall with 4 screws and spring washers
1)
(C-1)
.
3.3.2
Attaching either a conduit connection or cable
gland
1. Remove the protective cap from the cable entry.
2. Mount either a ¾"-14 NPT explosion-proof conduit connection or
a M25x1.5 flameproof gland to the cable entry.
1)
screws: either ¼" 20 UNC x ¾" or M6 x 1 x 20 mm
spring washers: either ¼" or M6
3.3.3

Attaching the flame detector to the tilt mount

► Illustration on the fold-out page (Figure C)
1. Place the flame detector with its cable entries pointing downwards
on the holding plate of the tilt mount (C-2).
2. Secure the flame detector to the tilt mount with the screw and a
spring washer using a 1/4" hex key (C-3).
3. Secure the flame detector with the locking screws (C-4, C- 5) using
a 3/16" hex key so that the flame detector can be wired.
3.3.4

Wiring the flame detector

For wiring, use color-coded conductors or suitable wire markings or
2
2
labels. 0.5 mm
to 3.5 mm
(12 to 20 AWG) wires may be used for site
wiring. The selection of wire gauge should be based on the number of
flame detectors used on the same line and the distance from the
control unit. For more information, please refer to the Technical
Manual.
► Illustration on the fold-out page (Figure B)
1. Make sure that the system is disconnected from the mains.
2. Remove the back cover by removing the 3 screws using a 3/16"
hex key (B-1).
The terminal board is now revealed.
3. Pull the wires through the cable entry.
4. Connect the wires to the corresponding terminals (see chapter 7.2
on page 21) on the terminal board using a 2.5 mm flat screw
driver.
5. Connect the earth wire to the earth screw using a 6 mm flat screw
driver (B-2). The flame detector must be well grounded.
6. Check the wiring. Improper wiring may damage the flame detector.
7. Check the wires for secure mechanical connection and press them
neatly against the terminal to prevent them from interfering while
closing the back cover.
8. Place and secure the back cover by screwing the 3 screws in the
cover bolts (B-1).
9. Perform a continuity test.
en
Use
13

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Flame 2100Flame 2350Flame 2370

Tabla de contenido