Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 74
en
Technical data
7.4.2

Other fuels

The flame detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 0.1 m
as 100% sensitivity.
For liquid fire – standard pan fire, size: 0.1 m
For gas flame – plume fire 0.75 m (30") high, 0.25 m (10") wide.
Maximum response time: 10 sec.
Detection distances of Dräger Flame 2100
Type of fuel
Gasoline
Methane (gas flame)
Liquefied petroleum gas (LPG, gas flame)
Hydrogen (gas flame)
Diesel fuel
Jet fuel (JP5)
Kerosene
Ethanol 95%
Isopropyl alcohol (IPA)
Polypropylene
Methanol
1)
Silane
Paper
gas flame: plume fire 0.5 m (20") high, 0.2 m (8") wide
1)
24
Detection distances of Dräger Flame 2350
Type of fuel
2
2
(1 ft
) and is defined
2
2
(1 ft
).
Gasoline
Isopropyl alcohol (IPA)
Liquefied petroleum gas (LPG, gas flame)
Jet fuel (JP5)
Max. distance
Kerosene
in meters (feet)
Diesel fuel
15 (50)
Polypropylene
13 (43)
Methane (gas flame)
13 (43)
Ethanol 95%
12 (39)
Methanol
11 (37)
Paper
11 (37)
11 (37)
11 (37)
11 (37)
10 (33)
7.5 (25)
7 (22)
6 (20)
Max. distance
in meters (feet)
20 (65)
16 (52)
15 (50)
15 (50)
15 (50)
15 (50)
15 (50)
13 (43)
12 (39)
12 (39)
7 (23)