The alarm delay option affects alarm relay, fault relay, and 0-20 mA
output. The status LED and outputs indicate warnings during the delay
time. When the delay time has passed, status LED and outputs
indicate the alarm.
Possible address setups
A system with up to 247 addresses can be configured.
Possible modes of operations
Function
Setting
Alarm Latch
YES: Enable alarm latching.
NO: Disable alarm latching (default).
1)
Automatic BIT
YES: Perform automatic & manual BIT
(default).
NO: Perform manual BIT only.
1)
Alarm BIT
YES: Successful manual BIT activates
the alarm relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the alarm relay.
2)
Auxiliary Relay
YES: Activate auxiliary relay at warning
level.
NO: Activate auxiliary relay at alarm
threshold (default).
(The auxiliary relay is latched only when the
programmable function Auxiliary Relay is
set to YES.)
1, 2)
Auxiliary BIT
YES: Successful manual BIT activates
the auxiliary relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the auxiliary relay
2)
EOL
YES: Auxiliary relay is used as End of
Line.
NO:
accordance with both auxiliary relay
and auxiliary BIT settings (default).
1)
not applicable for Dräger Flame 2370
2)
only available in wiring option 4 and 5
en
Use
Auxiliary
relay
operates
in
15