Desa CHAM55N Manual Del Usuario página 15

Decorative gas log chimenea
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

WARNING: Turn off log set and let cool before servicing. Only a
qualified service person should service and repair log set.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Log set is smoking/sooting
excessively
(Note: It is natural and unavoid-
able for vented gas log sets to
produce moderate levels of car-
bon (soot) where flames contact
the logs. This is especially true
with propane/LP gas.)
Burner is excessively noisy
(Note: The movement and com-
bustion of gas will create low,
unavoidable levels of noise.)
Burner flames are too low or
too high
901918-01J
TROUbLESHOOTING
POSSIBLE CAUSE
1. Poor fuel quality
2. Chimenea venting system not
drafting properly
3. Excessive flame impingement
or blockage
4. Improper fuel/air mixture
5. Excessive gas supply/pres-
sure
1. Passage of air/gas across ir-
regular surfaces
2. Obstructions in the primary air
openings of air mixer fitting
(propane/LP only)
1. Incorrect gas supply or pres-
sure
2. Blocked burner orifice or
burner manifold ports
3. Improper burner orifice size
www.desatech.com
REMEDY
1. Contact local natural or pro-
pane/LP gas company
2. Inspect chimenea vent and cap
for damage or blockage
3. Arrange the logs to allow flame
to pass in between the logs
4. Remove any foreign items in
and around the burner pan and
air mixer
5. Check for proper gas pressure
and correct orifice size
1. Relieve any tight bends or
kinks in gas supply lines
2. Remove any obstructions in
primary air mixer openings
1. Check for proper gas supply
pressure
2. Free burner orifice and mani-
fold ports of any burrs, paint,
or other blockage
3. Verify proper burner orifice siz-
ing (see Figure 10, page 10)
15

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Cham45pVc55anVc45apFc55anFc45ap

Tabla de contenido