Unit Start
Evap pump start
Evap flow switch consensus within
timer expiration
No
Unit Trip
Yes
Temperature control start
Temperature control stabilisation
Compressors start enabled
Control requires unit loading
New Compressor start required (see
loading table)
No
Compressors loading
Yes
New Compressors selection
Compressor line contactor closing
Transition confirmation within 10 sec
No
Compressor Trip
Yes
Compressor complete unloading
Pre-purge procedure
Pressure ratio exceeds minimum load
limit
No
Alarm delay timer expired
Yes
Compressor Trip
Yes
Compressor enabled to load
Control requires unit standby
Compressors standby
Control requires unit unloading
Compressor stop required (see
unloading table)
No
Compressors unloading
Yes
Compressor complete unloading
Pump-down procedure
Compressor line contactor opening
Arranque de la unidad
Arranque de la bomba del evaporador
Interruptor de flujo del evap. OK con expiración del tiempo
ajustado en el temporizador
No
Disparo de la unidad
Sí
Arranque del control de temperatura
Estabilización del control de temperatura
Arranque de los compresores activado
El control requiere la carga de la unidad
Se requiere un nuevo arranque del compresor (véase tabla de carga)
No
Puesta en carga del compresor
Sí
Nueva selección de compresores
Cierre del contactor de la tubería del compresor
Confirmación de la transición en 10 s.
No
Disparo del compresor
Sí
Descarga completa del compresor
Proceso de prepurga
La relación de presión supera el límite mínimo de carga
No
Retardo de alarma del temporizador expirado
Sí
Disparo del compresor
Sí
El compresor puede cargarse
El control requiere poner la unidad en standby
Standby del compresor
El control requiere la descarga de la unidad
Se requiere la parada del compresor (véase tabla de descarga)
No
Reducción de carga del compresor
Sí
Descarga completa del compresor
Proceso de recogida del refrigerante
Abertura del contactor de la tubería del compresor
57/92