Sime MURELLE HE 35 R M Manual Del Usuario página 106

Ocultar thumbs Ver también para MURELLE HE 35 R M:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

cer is between 1 and 1.5 bar.
If the load procedure has to be repea-
ted several times, it is advisable to
check that the seal of the heating cir-
cuit is intact (check that there are no
leaks).
– HIGH WATER PRESSURE ANOMALY
ALARM 03 (fig. 23/2)
If the pressure detected by the transdu-
cer is more than 2.8 bar, the boiler
stops and the display shows anomaly
"ALL 03"
– C.H. FLOW SENSOR ANOMALY
ALARM 05 (fig. 23/4)
If the C.H. flow sensor (SM) is open or
short circuited, the boiler will not func-
tion and the display will show the alarm
"ALL 05".
– FLAME BLOCK ALARM 06 (fig. 23/5)
If the flame control has not detected the
presence of the flame after a complete
ignition sequence, or for any other rea-
son the card cannot "see" the flame, the
boiler will stop and the display will show
the alarm "ALL 06".
Press the key
of the controls (2) to
start up the boiler again.
– SAFETY THERMOSTAT OR LIMIT THER-
MOSTAT ANOMALY ALARM 07 (fig.
23/6)
If the connection with the safety thermo-
stat/limit thermostat is interrupted, the
boiler will stop; the flame control will
remain waiting to be switched off for one
minute, keeping the system pump on for
that period.
If, the thermostat connection is restored
within the minute, the boiler will start up
working normally again, otherwise it will
stop and the display will show the alarm
"ALL 07".
Press the key
of the controls (2) to
start up the boiler again.
106
Fig. 23/1
Fig. 23/2
– PARASITE FLAME ANOMALY ALARM
08 (fig. 23/7)
If the flame control section recognises
the presence of flames also in phases
Fig. 23/4
when they should not be present, it
means there is a breakdown in the flame
detection circuit; the boiler will stop and
the display will show anomaly "ALL 08".
– WATER CIRCUL ATION ANOMALY
ALARM 09 (fig. 23/8)
There is no water circulation in the pri-
mary circuit. If the anomaly occurs upon
first request, the boiler performs a maxi-
mum of three attempts to assure the
presence of water inside the primary cir-
cuit; it then stops showing on the display
the ALL 09 anomaly.
If the anomaly occurs during normal
functioning, the display immediately
shows the ALL 09 anomaly, keeping the
plant pump and the eventual boiler
pump, switched on for 1 minute.
In this case there was a sudden increase
2
2
Fig. 23/7
Fig. 23/5
Fig. 23/6
of the boiler inner temperature. Check to
see if there is water circulation inside
the boiler and check if the pump is ope-
rating properly.
To exit the anomaly press the
ton of the controls (2). If the anomaly
persists, request assistance from quali-
fied technical personnel.
2
– AUXILIARY
SENSOR
ANOMALY
but-
Fig. 23/8

Publicidad

Tabla de contenido
loading

Tabla de contenido