Mitsubishi Electric MXZ-6D122VA2 Manual De Instalación página 4

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
1.
Obstacles above
When there is no obstacle in front and
on the sides of the unit, it is allowed
to install the unit where an obstacle is
above the unit only if the space shown
in the figure is provided.
3.
Obstacles in front (blowing) only
When there is an obstacle in front of
the unit as shown in the figure, open
space above, behind, and on the sides
of the unit is required.
5.
Obstacles in front, behind and on side(s)
• When installing the unit in an area that is enclosed with walls such
as a verandah, be sure to have enough space as shown below.
In this case, the air conditioning capacity and power consumption
might deteriorate.
• When there is a lack of airflow or there is a possibility of becoming
short cycle, install an outlet guide and make sure there is enough
space behind of the unit.
• When installing two or more units, do not install the units in front or
behind each other.
100 or more
Height of the obstacle is 1200 or less
En-3
100 or more
500 or more
500 or more
200 or more
350 or more
500 or more
500 or more
2.
Front (blowing) side open
As long as space indicated
in the figure is provided, it
is allowed to install the unit
where obstacles are behind
and on the sides of the unit.
(No obstacle above the unit)
100 or more
4.
Obstacles in front and behind
The unit can be used by at-
taching an optional outdoor
blowing guide (PAC-
SH96SG-E) (but both sides
and top are open).
6.
Service space
Provide space for service and maintenance as shown in the figure.
Service space
100 or more
100 or more
350 or more
200 or more
350 or more
100 or more
500 or more
Blowing guide (PAC-SH96SG-E)
500 or more
350 or more
(Unit: mm)

Publicidad

Tabla de contenido
loading

Tabla de contenido