DESCRIPTION OF THE UNIT
MACHINE PURPOSE
The fan coil is a room air treatment terminal unit for both winter and summer operation.
AVAILABLE SIZES
The FCXI_AS fan coils are available in:
5 sizes
with 3-row coil
FCXI 20 AS
FCXI 30 AS
FCXI 40 AS
FCXI 50 AS
FCXI 80 AS
FCXI_AS
: without control panel and with Inverter motor, 3-row
heat exchanger, high cabinet for vertical installation, varnished
with anti-corrosion polyester powder (colour RAL 9002). The
delivery grille and the feet for floor-standing solutions (ZX ac-
cessory) are made of plastic of the colour RAL 7044. Requires
external control panel (accessory).
TECHNICAL DATA AND OPERATING LIMITS
FCXI
Maximum water inlet temperature
Maximum recommended water inlet temperature
Maximum operating pressure
Minimum water flow rate
Maximum water flow rate
Room temperature limits (Ta)
Relative humidity limits in the room (R.H.)
Power supply
Performance values refer to the following conditions:
- at the maximum motor speed;
Water temperature
In order to prevent air stratification in
the room, and therefore to achieve
improved mixing, it is advisable not
Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment
where the relative humidity is high,
condensate might form on the air
delivery and on the outside of the
device. This condensate might be
deposited on any objects underneath
and on the floor.
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Wet bulb ambient
air temperature
IFCXIUASLJ 1210 - 5383600_04
14
The FCXI_U fan coils are available in:
5 sizes
with 3-row coil
FCXI 20 U
FCXI 30 U
FCXI 40 U
FCXI 50 U
FCXI 80 U
FCXI_U
heat exchanger, universal cabinet for vertical fl oor-standing in-
stallation or wall-mounting, varnished with anti-corrosion pol-
yester powder, colour RAL 9002. The air delivery and suction
grilles are made using plastic material in colour RAL 7044.
Requires external control panel (accessory).
FCXI 20U ÷ 50U
°C
°C
bar
l/h
l/h
°C
- the total input power is determined by adding the input power
for the unit and the input power for the accessories connected
and declared in the corresponding manuals.
to supply the fan coil with water at a
temperature over 65°C.
The use of water at high temperatures could
cause squeaking due to the different
To avoid condensate on the external
structure of the device while the fan is
functioning, the average temperature
of the water must not be lower than
the limits shown in the table below,
that depend on the thermo-hygrometric
conditions of the air in the room.
The limits mentioned above refer to
operation while the fan is set to its
15
17
19
21
23
: without control panel and with Inverter motor, 3-row
20
30
40
80°
65°
8
100
100
150
750
750
1100
0° < Ta < 40°
R.H. < 85%
230 V ( ±10% ) ~ 50 Hz
thermal expansions of the elements
(plastic and metal), this does not however
cause damage to the unit if the maximum
operating temperature is not exceeded.
minimum speed level.
In the event of prolonged fan inactivity
and with cold water passing through
the coil, condensate may form on the
external case of the unit. As a result,
we recommend including the 3-way
valve accessory.
Dry bulb ambient air temperature
21
23
25
3
3
3
3
3
3
3
3
3
6
5
4
-
8
7
FCXI 80U
50
80
150
300
1150
2200
27
29
31
3
3
3
3
3
3
3
3
3
3
3
3
6
5
5