Connection With Pco5 - AERMEC AERWEB300 Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Connection with pCO
5
GPRS antenna
for AERWEB300
with GPRS modem on board
RS485 connection
AERWEB300 Board
AER485P2 Board
Signal "+", 13
Signal "+"
Signal "-",12
Signal "-"
Do not connect the "gnd" signal
Do not connect the cable braid
The maximum length of the entire connection (including all
the connected boards) = 1200 m
LAN connection
RS485 connection (J25-BMS2)
5
pCO
Electric power supply
L-N (230V
)
AC
AER485P1
RS485 connection with
any other boards
ATTENTION: The connection can be performed directly on the connection J25-BMS2. It should also provide
!
for setting the serial parameters and Communication on / e card / and pCO5, refer to user manual for details.