Installation and electrical connection

DANGER! Danger of death!
Incorrect installation and electrical connection can result in fatal injury.
• Installation and electrical connection may only be carried out by qualified
personnel and in accordance with the applicable regulations!
• Adhere to regulations for accident prevention!
9.1

Installation

• Only install the pump after all welding and soldering work has been completed
and, if necessary, the pipe system has been flushed through.
• Install the pump in a readily accessible place for easy inspection and dismantling.
• When installing in the feed of open systems, the safety supply must branch off
upstream of the pump (DIN EN 12828).
• Install check valves upstream and downstream of the pump to facilitate a possi-
ble pump replacement.
• Perform installation so that any leaking water cannot drip onto the control
module,
• To do this, aline the upper gate valve laterally.
• In thermal insulation work, make sure that the pump motor and the module are
not insulated. The condensate-drain openings must remain uncovered.
• Install the pump with the power switched off and the pump motor in a horizon-
tal position see Fig. 3 for installation positions of the pump.
• Direction arrows on the pump housing indicate the direction of the flow.
9.2

Electrical connection

DANGER! Danger of death!
A fatal shock may occur if the electrical connection is not made correctly.
• Only allow the electrical connection to be made by an electrician approved
by the local electricity supplier and in accordance with the local regulations in
force.
• Disconnect the power supply before any work.
• The current type and voltage must correspond to the details on the name plate.
• Maximum back-up fuse: 10 A, slow bow.
22
• Earth the pump according to the regulations.
• Mains connection: L, N, PE
Note:
For information on connecting the mains and signal cables see chap.2.4
10

Commissioning

WARNING! Risk of injury and damage to property!
Incorrect commissioning can lead to injuries to persons and damage to property.
• Commissioning by qualified personnel only!
• Depending on the operating status of the pump or system (fluid temperature),
the entire pump can become very hot.
Touching the pump can cause burns!
11

Maintenance

DANGER! Danger of death!
A fatal shock may occur when working on electrical equipment.
• The pump must be electrically isolated and secured against unauthorised
switch-on during any maintenance or repair work.
• Any damage to the connecting cable must always be rectified by a qualified
electrician only.
After successful maintenance and repair work, install and connect the pump ac-
cording to the "Installation and electrical connection" chapter. Switch on the pump
according to the "Commissioning" chapter.