RS-232 Communications Protocol & Command Set
SET AVR MODE
Sets AVR (Automatic Voltage Regulation) MODE.
Command:
_________________________________________
If specified mode is invalid
Action:
Response from UPS:
_________________________________________
SET FEEDBACK MODE
Sets the feedback mode to ON (unsolicited) or OFF (polled).
When ON, a message will be sent to the controller every time the
status of an input (i.e. button), output (i.e. outlet) or power state
(i.e. overvoltage) changes.
If feedback is OFF, the controller must request status with a query
(see Queries section for more details).
Send to UPS:
_________________________________________
If specified mode is invalid
Action:
Response from UPS:
_________________________________________
SET LINEFEED MODE
With LINEFEED MODE set, a linefeed character (<LF>, 10d, 0Ah)
is appended to each response.
Send to UPS:
_________________________________________
If specified mode is invalid
Action:
Response from UPS:
_________________________________________
!SET_AVR mode<CR>
mode = {OFF, STANDARD, SENSITIVE}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$AVR = mode <CR>
!SET_FEEDBACK mode<CR>
mode = {ON, OFF}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$FEEDBACK = mode<CR>
!SET_LINEFEED mode<CR>
mode = {ON, OFF}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$LINEFEED = mode<CR>
SET METER BRIGHTNESS
Sets the LCD display and outlet bank indicator brightness.
Send to UPS:
_________________________________________
If specified brightness setting is invalid
Action:
Response from UPS:
_________________________________________
SET DISPLAY SCROLL MODE
Sets the LCD display SCROLL mode
Send to UPS:
_________________________________________
If specified display scroll mode is invalid
Action:
Response from UPS:
_________________________________________
SET DISPLAY SLEEP MODE
Sets the LCD display SLEEP mode
Command:
If specified display sleep mode is invalid
Action:
Response from UPS:
_________________________________________
10
!SET_BRIGHT xxx<CR>
xxx = {100, 075, 050, 025}
No action will be taken, UPS will
request a valid brightness setting
$INVALID_PARAMETER<CR>
$BRIGHTNESS = xxx<CR>
!SET_SCROLLMODE xxx<CR>
xxx = {5SEC, 10SEC, OFF}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$SCROLL_MODE = xxx<CR>
!SET_SLEEPMODE xxx<CR>
xxx = {30SEC, 60SEC, OFF}
No action will be taken, UPS will
request a valid mode setting
$INVALID_PARAMETER<CR>
$SLEEP_MODE = xxx<CR>