RS-232 Communications Protocol & Command Set
RESET FACTORY SETTINGS
Resets all of the custom configuration settings
Send to UPS:
Action:
values
Response from UPS:
_________________________________________
QUERIES
IDENTIFY
Request that the unit identify itself.
Send Query to UPS:
Action:
will be provided.
Response:
_________________________________________
OUTLET STATUS
Requests the on/off status of the outlet banks
Send Query to UPS:
Action:
Response:
_________________________________________
!RESET_ALL<CR>
Sets all state variables to the default
$FACTORY SETTINGS
RESTORED <CR>
?ID<CR>
Model number and firmware revision
$PANAMAX<CR>
$MB1000<CR>
$FIRMWARE revision<CR>
?OUTLETSTAT<CR>
status = {ON, OFF}
On/Off status for outlets
will be provided.
$BANK1 = status<CR>
$BANK2 = status<CR>
POWER STATUS
Requests the status of the input voltage. The responses are the
same as Power Fault Status Change.
Send Query to UPS:
Action:
Response:
NORMAL<CR>
Overvoltage
Undervoltage
Lost Power
Test Mode
_________________________________________
VOLTAGE
Requests the input and output voltages
Send Query to UPS:
Action:
Response:
xxx is expressed in decimal format. If the value is less than 100,
the hundreds digit is represented with a 0. For example a line
voltage of 92VAC would be expressed as: $VOLTAGE =092
_________________________________________
LOAD LEVEL STATUS
Requests the load level, expressed as percentage of maximum.
Send Query to UPS:
Action:
Response:
xxx is the load level (percentage of maximum load) expressed in
decimal format. If the value is less than 100, the hundreds digit
is represented with a 0.
_________________________________________
11
?POWERSTAT<CR>
Power status messages will be
returned
Normal operation $PWR =
$PWR = OVERVOLTAGE<CR>
$PWR = UNDERVOLTAGE<CR>
$PWR = LOST POWER<CR>
$PWR = TEST<CR>
?POWER<CR>
Voltage status messages will be
displayed
$VOLTS_IN = vvv<CR>
$VOLTS_OUT = vvv<CR>
$WATTS = xxxx<CR>
$VA = xxxx<CR>
?LOADSTAT<CR>
Load level will be displayed
$LOAD = xxx<CR>