Installing Your UPS

HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt.
However, recharging the battery for at least four hours is recom-
mended to insure that the battery's maximum charge capacity is
achieved. Charge loss may occur during shipping and storage.
To recharge the battery, simply leave the unit plugged into an
AC outlet. The unit will charge in both the ON as well as the OFF
position. If you wish to use the software, connect the enclosed
USB cable to the USB port on the UPS and an open USB port on
the computer.
2. With the UPS unit OFF and unplugged, plug your equipment
into the unit's rear panel AC outlets. DO NOT plug a space heater,
vacuum cleaner, paper shredder or other large electrical device
into the UPS. The power demands of these devices will overload
and possibly damage the unit.
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall
outlet). Make sure the wall branch outlet is protected by a fuse
or circuit breaker and does not service equipment with large
electrical demands (e. g. refrigerator, copier, etc.) Avoid using
extension cords. If used, the extension cord must be UL or CSA
Listed, minimum 14 AWG, 3-wire grounded, and rated for 15
Amps.

Specifications

Input
Voltage..............................................................................85 – 137 Vac
Frequency..............................................................................57 – 63 Hz
AC Power
Current Rating................................................................................12 A
Surge Protection...................................................................900 Joules
Overvoltage Shutoff, fast rise.................................................150 ± 5 V
Overvoltage Shutoff, slow rise................................................132 ± 5 V
Undervoltage Shutoff................................................................90 ± 5 V
Automatic Voltage Regulation,
Sensitive Mode Capture Range.............................................99 – 135 V
Automatic Voltage Regulation,
Sensitive Mode Output Range................................................120 ± 5%
Automatic Voltage Regulation,
Standard Mode Capture Range............................................94 – 142 V
Automatic Voltage Regulation,
Standard Mode Output Range..............................................120 ± 10%
Bank 1 EMI Filtration......................................66dB Max, 100kHz-2MHz
Bank 2 EMI Filtration......................................66dB Max, 100kHz-2MHz
4. Press and hold the power switch for 2 seconds to turn the
UPS on. The display will say "Initializing", followed by the
normal operation screen.
5. The rear panel circuit breakers will open and power to the
connected equipment will be turned OFF if an overload is
detected. To correct this, turn the UPS off, unplug at least one
piece of equipment, wait 10 seconds, check to make sure that the
circuit breakers are reset, and turn the unit on.
6. The UPS will automatically charge the battery whenever it is
plugged into an AC outlet.
7. To maintain optimal battery charge, leave the UPS plugged
into an AC outlet at all times.
Note: To store your UPS for an extended period, cover it and
store with the battery fully charged. Recharge the battery every
three months to ensure battery life.
UPS Output
Voltage...................................................120 ± 5 V Simulated Sine Wave
Frequency..............................................................................60 Hz ± 1%
UPS Output Capacity...........................................1000VA 600W @ 0.6pf
UPS Backup Time...................................................3 minutes at full load
Transfer Time...............................................................................< 10ms
2