PUMPTEC-PLUS Pump Protection System
C. Red Light
The red light (C) indicates a line voltage fault occurred and Pumptec-Plus has turned off the pump
motor.
A SOLID RED LIGHT indicates an under voltage condition (line< 207 VAC) existed for more than 2.5
seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET
BUTTON (D) may also be pressed to clear this condition.
A FLASHING RED LIGHT indicates an over voltage condition (line> 253 VAC) has existed more than
2.5 seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET
BUTTON (D) may also be pressed to clear this condition.
B & C. Red and Yellow Flashing Lights
If the RED and YELLOW lights (B & C) are flashing on and off together, a rapid cycle condition was
detected. A rapid cycle condition is defined as four or more motor starts per minute.
RESET BUTTON
D. Reset Button
The reset button is used to restart the Pumptec-Plus from a tripped condition. Pressing the reset
button for less than ten seconds has no effect on the calibration. Simply press and release the
button. The unit will reset.
Pressing the reset button for more than 10 seconds will cause the unit to go into the calibration
mode. A rotating light sequence from green to yellow to red will begin. At this point, the contactor
closes and the motor will start to run. The unit will stay in the calibration mode for 3 minutes or
until the reset button is pressed again.
If after three minutes the reset button is not pressed, the unit will revert back to its normal running
mode, making no changes to the calibration.
Pressing the reset button before the three minute period expires will cause the unit to recalibrate to
the motor load present at the time the reset button is pressed the second time.