Foreman Ductable Dual Fuel Indirect-Fired Heater
6. Do not locate fuel gas containers or fuel supply
hoses within 20 feet/6 meters of the heater's
blower outlet.
7. Do not direct the heater toward any propane gas
container within 20 ft. (6m) of the heater's air
discharge. When ducting is attached to the heater,
the heater's hot air discharge is the end of the
ducting.
8. Do not block air intakes or discharge outlets of the
heater. Doing so may cause improper combus-
tion or damage to heater components leading to
property damage.
9. The hose assembly shall be visually inspected on
a daily basis after heater relocation and when the
heater is in use. If it is evident there is excessive
abrasion or wear, or if the hose is cut, it must be
replaced prior to the heater being put into opera-
tion. The hose assembly shall be protected from
building materials, and contact with hot surfaces
during use. The hose assembly shall be that
specifi ed by the manufacturer. See parts list.
10. Check for gas leaks and proper function upon
heater installation, when relocating, and after
servicing. Refer to leak check instructions within
installation section of this manual.
11. This heater should be inspected for proper
operation by a qualifi ed service person before
each use and at least annually.
12. Always turn off the gas supply to the heater if the
heater is not going to be used.
13. This heater is wired with a ground connection for
your protection against shock hazard and must
be wired directly into a properly grounded electri-
cal supply. Failure to use a properly grounded
electrical supply can result in electrical shock,
personal injury, or death.
14. If gas fl ow is interrupted and fl ame goes out,
do not relight the heater until you are sure that
all gas that may have accumulated has cleared
away. In any event, do not relight the heater for
at least 5 minutes.
15. The heater requires a minimum 500 gallon/1892
liter propane tank for proper gas supply pressure
and operation. A larger tank may be required
depending upon operating temperature condi-
tions at the site.
16. When the heater is to be stored indoors, the
connection between the propane gas supply
container and the heater must be disconnected.
The container must be removed from the heater
and stored in accordance with NFPA 54 National
Fuel/Gas Code, Standard for the Storage and
Handling of Liquefi ed Petroleum Gases, ANSI/
NFPA 58, or CSA B149.1 Natural Gas and
Propane Gas Installation Code.
17. Propane gas supply containers have left handed
threads. Always use the appropriate wrench to
make a connection to tighten or loosen the pigtail
connector's P.O.L. fi tting at the container's gas
supply valve.
18. The heater may start at any time when used with
a thermostat.
Owner's Manual • Foreman
9