Daikin RZQ18PVJU8 Manual Del Usuario página 11

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Do not let any refrigerant other than the specifi ed refrigerant
enter the refrigerant system.
Do not let any gas such as air enter the refrigerant system.
〈Precautions when connecting the piping〉
See the following table for fl are dimensions.
When connecting the fl are nuts, apply refrigeration oil to the
inside of the fl ares and turn them three or four times at fi rst.
(Use ester oil or ether oil.)
See the following table for tightening torque. (Applying too
much torque may cause the fl ares to crack.)
After connecting all the piping perform a gas leak check by
using nitrogen.
Tightening
Flare dimension
Pipe size
torque (ft·lbf)
φ3/8"
26.7 ± 2.6
0.504 - 0.520
φ5/8"
50.6 ± 5.0
0.760 - 0.776
Apply ester oil or ether oil
only to inner side of flare.
If you are obliged to install the unit without a torque wrench,
you may follow the installation method mentioned below.
After the work is fi nished, make sure to check that there is
no gas leak.
When you keep on tightening the fl are nut with a spanner,
there is a point where the tightening torque suddenly in-
creases.
From that position, further tighten the fl are nut the angle
shown below.
Tightening angle
Pipe size
(Guideline)
φ3/8"
60°~90°
φ5/8"
30°~60°
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, oil and
eventual other parts should be comply the relevant local and
national regulations.
6-4
Refrigerant piping work procedure
The fi eld piping can be connected in three directions.
Screw for
front panel
Front direction
Screw for piping
cover (front)
When connecting the piping downward, remove the knock-
out hole by making four holes in the middle on the each side
of the knockout hole with a drill.
English
Flare shape (in.)
A (in.)
R0.016
~0.031
Recommended arm
length of tool (in.)
Approx. 7 7/8
Approx. 11 13/16
Front
panel
Piping cover
Lateral
direction
Downward
direction
Drill
Middle on the side
Knockout hole
Slit
Then cut out the corner of the bottom frame along the slits (in
two positions) by using a hacksaw.
After removing the parts, it is recommended to apply repair
paint on the edges, to prevent rusting.
Cautions on connecting the connection piping
When it is expected that water condensed in the stop valve
will reach the indoor unit through the gap between the heat
insulating material and the piping (for example, when the
outdoor unit is installed in a higher position than the indoor
unit), take proper action such as caulking the connection
area.
[Measures to prevent invasion of small creatures and litter]
Block all gaps in the piping penetration areas with putty or
heat insulating material (arranged in the local fi eld) as
shown in the fi gure below.
(If small creatures such as insects or litter enter the outdoor
unit, a short-circuit may be caused inside the control box.)
6-5
Heat insulation of piping
Make sure to insulate the fi eld piping (on both the liquid line
and gas line) and refrigerant branching kit.
(If they are not insulated, water leakage may be caused.)
(The maximum temperature of the piping on the gas line is
about 248 °F during heating operation. Use an insulation
suffi ciently resistant to this temperature.)
Reinforce the refrigerant piping according to the installation
environment. If it is not reinforced, condensate may form on
the surface of the insulation.
WARNING
Make sure to insulate the fi eld piping up to the piping con-
nection area inside the unit. If the piping is exposed, dew
condensation and burn by contact may be caused.
6-6
Airtight test and vacuum drying
The unit has been checked for leaks by the manufacturer.
Confi rm that the valves are fi rmly closed before airtight test or
vacuumdrying.
To prevent entry of any impurities and insure suffi cient pres-
sure resistance, always use the special tools dedicated for
R410A.
Slit
Field piping
Bottom frame
Putty or heat
insulating material
(arranged in local field)
10

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Rzq24pvju8Rzq30pvju8Rzr18pvju8Rzr24pvju8Rzr30pvju8

Tabla de contenido