EN – Installation instructions
The radiator may only be installed by a special-
ist.
Safety instructions
Read these instructions thoroughly prior to
►
installation/commissioning.
After installation, pass the instructions on
►
to the end user.
WARNING
Risk of injury!
Note the weight of the radiator (see
►
manufacturer's data).
At 25 kg and above, the work should be
►
carried out with lifting equipment or by
several persons.
Conditions of use
Observe the operating conditions for wa-
►
ter heating installations as defined in
DIN 18380 "VOB German Contract Proce-
dures for Building Services".
Maintain water quality as defined in VDI
►
2035 "Prevention of damage in water heat-
ing installations".
Observe the limitations for use in damp
►
rooms as defined in DIN 55900 "Coatings
for radiators".
Use radiator only in closed heating systems.
►
Store and transport radiator only in the
►
protective packaging.
Observe minimum clearances between ra-
►
diator and surrounding objects for air cir-
culation.
Complaints
Please contact the supplier.
►
Disposal
Packaging and any parts that are not need-
►
ed should be recycled or disposed of prop-
erly. Observe local regulations.
Technical features
•
Operating pressure: max. 10 bar
•
Test pressure: 1.3 x operating pressure
•
Flow temperature: hot water up to
110°C (230°F)
Directions for installation
Protect radiator from damage
When installing, only remove protective
►
packaging at the fastening and connection
points.
Only remove protective packaging com-
►
pletely during final cleaning or prior to
commissioning.
Fixing
For radiators with lugs: Note the number
►
and positions of fixing points (see Fig. A).
Install mounting material according to
►
separate installation instructions.
Compact radiator connection
Unscrew painted blanking plugs at the des-
►
ignated connection points.
Note: Do not install Therm X2
plugs in radiators with a height of 200.
For multilayered radiators and twinwire or
►
alternating connection: Install accompany-
ing Therm X2
separating plugs (see sepa-
®
rate installation instructions).
Connect radiator with commercially avail-
►
able fittings upstream.
Tightly cap open connections with air vent
►
plugs (top) and blanking plugs.
Only existing blanking plugs may be used on
Kermi steel panel radiators.
Valve radiator connection
Valve with factory pre-set k
facturer's data).
Air vent plugs (top) and blanking plugs are fac-
tory pre-assembled.
Remove painted caps on the valve mount-
►
ings and dispose of, as they must not be
used as seals on the radiator.
Connect radiator with commercially avail-
►
able fittings upstream on the valve mount-
ings.
separating
®
value (see manu-
V