The length of connection cables from the motors to the control panel unit must not exceed 15 m. The wire section of the motor power supply must be
1.5 mm
, whilst that of the accessories must be 0,75 mm
2
(for example type ÖLFLEX-110 CH - Cod.ACG2133). It is compulsory to use shielded cable for the encoder in order to guarantee the correct operation
of the control board. The shield of the ENCODER cable must be earth grounded at one end (not to the card GND), and at the opposite end the
shield must be free (conductor not connected).
To ensure the correct functioning of the installation it is advisable to wire encoder and motor with separate cables.
DIP 7 ON - Current sensors Off / Encoder On
DIP 7 OFF - Current sensors On / Encoder Off
J1
AERIAL
Radio antenna
COM
Common contact unit
PHOT.1 NC
Photocell contact (NC)
STOP
Stop button contact (NC)
OPEN
Opening button contact (NO)
CLOSE
Closing button contact (NO)
K BUTT.
Single pulse contact (NO)
A+D+
Positive for accesories supply: 24Vdc
A-D-
Negative for accessories supply: 24Vdc
Wiring of flasher 24Vdc
(code ACG7061)
(FOLLOW THE POLARITY)
Wiring battery status led (12Vdc)
SIGNAL BATTERY
SIGNAL
Lamp gate open (12Vdc 3W max)
SIREN
Wiring intrusion alarm siren (12Vdc max 300mA)
Wiring acoustic warning (12Vdc max 200 mA)
BUZZER
LOCK
Electric lock connection (Max 15W 12V)
J2
Connector for battery charge card, 24Vdc (code
BATTERY CHARGER
ACG4648)
J3
EXP. 12V
Connector
ACG5471)
J4
Connector for radio receiver, supply 24Vdc
RADIO
WARNING!
. As for the encorder it is very important to use a shielded wire with a section of 0,75 mm
2
for
EXPANDER
card
(code
J5
MOTOR 1
Wiring MOTOR 1 (no polarity)
MOTOR 2
Wiring MOTOR 2 (no polarity)
J6
SEC.TRANSF.
Connector for transformer secondary
J7
ENCODER
Connection block for wiring of ENCODER M1and M2
S-M1
Signal ENCODER M1
+ M1
Positive supply ENCODER M1
GND
Negative supply ENCODER M1 and M2
+ M2
Positive supply ENCODER M2
S-M2
Signal ENCODER M2
J8
SW
Connector for factory encoding. Do not alter the
position of the jumper located as shown in
figure
JP5
Verify that the jumper is inserted !
J9
L1 - N
Supply 230 Vac 50/60Hz (external to the card)
(on request 120V/60Hz)
LS
LOW SPEED
Electronic regulator for low speed
JP1
Selection of motor type for operation with current
sensor M1
JP2
Selection of motor type for operation with current
sensor M2
JP3
Selection of operation with 1 or 2 motors (default
closed jumper 2 motors)
M1
Current sensor regulator for motor 1
M2
Current sensor regulator for motor 2
G G
B B
2
Jumper position for
PRINCE with Current
sensors
Jumper position for
PRINCE with
Encoder

Publicidad

Tabla de contenido
loading