1. Safety Instructions

For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard
and, where applicable, in acc.with
IEC 60079-17 on electrical apparatus for ex-
plosive atmospheres.
The light fittings must not be operated in
Zones 0 and 20!
The technical data indicated on the luminaires
are to be observed!
Changes of the design and modifications to
the light fittings are not permitted!
The light fittings shall be operated as
intended and only in undamaged and perfect
conditions!
Only genuine Cooper Crouse-Hinds, S.A. spa-
re parts may be used for replacement!
Repairs that affect the explosion protection,
may only be carried out by
Cooper Crouse-Hinds, S.A. or a qualified
"electrician" and will subsequenctly have to
be checked by an "expert"!
Do not open if energized!
Do not keep these operating instructions
inside the light fitting during opertion.
The national safety rules and regulati
The national safety rules and r
The national safety rules and r
The national safety rules and r
The national safety rules and r
egulati
egulati
egulations for
egulati
prevention of accidents and the following
safety instructions which are marked with an
(
) in theses operting instructions,will have
to be observed!
2. Conformity with standards
This explosion protected light fittings meets the
requeriment of IEC/EN 60079-1, IEC/EN 61241
and EN60598.
It also complies with the EC Directives
for "Apparatus and protective systems for use in
explosive atmospheres" (94/9/EC) and
"Electromagnetic compatibility" (2004/108/EC).
It has been designed, manufactured and tested in
accordance to the state of the art and according
to EN29001 (ISO9001).
The light fittings are suitables for use in explosive
atmospheres,
Zone 1 and 2 acc. to IEC 60079-10-1 and
Zones 21 and 22 acc. IEC 61241-10-2.
3. Technical data
Application:
Ex II 2 GD
Ex d e ib IIB T5
Ex tD A21 IP66 T100°C
Certificates:
LOM 09 ATEX 2062X
Types:
See Table 1
Lamps to be use:
See Table 1
Approval of the product.
ATEX Quality assurance:LOM 02 ATEX 9040
Degree of protection
acc. EN60529:
IP 66
Insulation class
acc. EN60598:
I
Permissible ambient
temperature:
-20
C to +55
o
Permissible ambient
temperature battery
(specified data):
-5ºC to +35ºC
Rated voltage:
220V- 240V
Frequency
50 - 60Hz
Power factor :
>= 0.95
Rated current:
18 W
36 W
Circuit:
EVG, with emergency
powersupply
Light efficiency:
73 % in normal operation
Intensive sun radiation in areas of high ambient
1)
temperatures may cause inadmissible tempera-
ture rise inside of the luminaire. This may result a
decrease in lifetime of the electronic components
and battery. Therefore those luminaires should be
switched off during daytime by a photocell control.
6
Lamp cap:
Material of enclosure:
Material of glass:
Storage temperature in
original Packing
Terminals capacity:
Entries of cables
Direct entry:
Dimensions:
Operation in emergency mode:
Rated emergency lighting 1 lamp duration
Light output:
1.5 h
3.0 h
Charging duration:
Battery type:
18 W (1.5 h and 3.0 h) -> 5x 4 Ah - NiCd
36 W (1.5 h) -> 5x 4 Ah - NiCd
36 W (3.0 h) -> 5x 7 Ah - NiCd
4. Installation
The respective national regulations as well
as the general rules of engineering which apply
to the installation and operation of explosion
protected apparatus will have to be observed.
Transport and storage of the light fitting is
permitted in original packaging only!
Pay attention when mounting or repairing the
light fitting, don´t damage the fire-finish of the
glass adquired during moulding (abrasions,
sanding, etc.) that can weaking their
mechanical functions!
Number maximum of light fittings with electronic
ballasts: See table 2
The light fittings are suitable for a wall and for a
ceiling installation.
The light fittings have to be only mounted
horizontally, or with the cable entry from below
for the wall installation.
4.1 Opening and closing the
luminaires
The opening of light fitting always shall be
without voltage!
For opening and closing the light fitting see
secuency fig 3.
The light fitting is well closed when the cover
is completly threaded on the luminaire
enclosure!
Dimensions for mounting: See figure 2
Accesories for mounting:
See Cooper Crouse-Hinds, S.A. catalogue
4.2 Cable entries
Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type and
dimensions of the main connection cable,
C
1)
o
following their manufacturer instructions.
The cable entries devices has to be the
certified protection mode ''Exd'' !
1)
+
10%; AC
Unused cable entries have to be closed by a
correspondant ''Exd'' certified blanking plug!
0.18 A
If the original blanking plugs are used, these
0.36 A
must be tightened to the enclosure of light
fitting with a 15 Nm torque!
G13 acc IEC 60081
Cooper-free aluminium
painted polyester grey.
Borosilicate
-40
o
C up to +60
o
C
2 x 2.5 mm
2
PE ext.: 2 x 4 mm
2
2 x ¾" NPT,
one plugged
See figure 1.
1.5 h or 3.0 h
18 W
50 %
36 W
32 %
18 W
29 %
36 W
18 %
> 14 h

4.3 Mains connection

See wiring diagram.
-Observe the isolation inside the light fittings acc. to
( EN 60598-1, EN 60079-0 / 6.1 remark 3)
-Flexible cables shall be used with trumpet-
shaped cable glands or other suitable entries with
additional pull-relief. (min. protection IP66)
If multi- or fine-wire conneting cables are used,
the wire ends will have to be handled in acc. with
the applicable national and international rules.
(e.g. use of sleeves for strands).
In order to maintain the explosion category, the
conductors will have to be connected with
special care.
The insulation shall reach up to terminal.
The conductor itself must not be damaged.
4.4 Lamps mounting
Only must be mounting apropiated lamps for
Only must be mounting apr
Only must be mounting apr
Only must be mounting apr
Only must be mounting apr
opiated lamps for
opiated lamps for
opiated lamps for
opiated lamps for
the supplied light fitting. See indications in the
general label of the luminaire and in the
present instructions!
5.
Taking into operation
Prior to operation check the light fitting for its
proper functioning and installation in
compliance with these operating instructions
and others applicable r
others applicable regulations!
others applicable r
others applicable r
others applicable r
egulations!
egulations!
egulations!
egulations!
Only carry out insulation measurements between
PE and external conductor L1 (L1, L2, L3) as well
as between PE and N.
- measurement voltage: max. 1kV AC/DC
- min. insulation: 2 MΩ
Then the light fitting have to be tightly closed.
Before the first operation, the battery have to be
charged 14 h.
6. Function

6.1 Emergency operation

The duration of the emergency operation is
factory side fixed and can not be adjusted.
The emergency operation will automatically
started when main voltage falls under 75 % for
more than 100 ms or the charging line L L L L L is
switched off (see wiring diagram).
6.1.1
Function test emergency
light
Switch off the mains supply from light fitting.
The emergency lamp will operate.
A function test should not exceed the following
test periods:
Battery set for 1,5 h emergency light: 60 min.
Battery set for 3,0 h emergency light: 120 min.
Should the emergency lamp be extinguished
within the test period though the battery is fully
charged, the latter will have to be replaced by a
new battery set.
6.2
Charging
At temperatures below -5°C and above +35°C the
battery will not be fully charged for
electrochemical reasons.
Note: New batteries will reach their total
useful capacity only after 3 charging/
discharging cycles.