Example: if data would be the following:
Addr
0x0103
And password is "111" it would be:
• as ASCII coded sequence (excluding prefix 0x intending hexadecimal data):
31 31 31 FF
Where the significant characters are the first 3, byte FF could have any value.
• Request pack (2 word starting from register 0x0103 to Sentinel addressed 1) and related reply pack with overmentioned 3 character string
"111" would be:
Request: 01 03 01 03 00 02 35 F7
Reply: 01 03 04 31 31 31 FF F0 D0
Time
Time is a 7 byte array where byte are located, in receiving order, as follows:
0 - SECONDS (0..59)
1 - MINUTES (0..59)
2 - HOURS (0..23)
3 - DAY OF WEEK (1=MONDAY..7=SUNDAY)
4 - DAY OF MONTH (1..31)
5 - MONTH (1..12)
6 - YEAR (0..99, 00=2000)
Alarm
Alarm is used in the alarm history. This data contains data, hour and alarm code. It is a 6 byte array where byte are located, in receiving order,
as follows:
0 - DAY OF MONTH (1..31)
1 - MONTH (1..12)
2 - YEAR (0..99, 0=2000)
3 - HOURS (0..23)
4 - MINUTES (0..59)
5 - ALRMCODE
In case ALRMCODE is null, this data contains no alarm.
The following tab indicathe the coding referred to byte ALRMCODE
ALRMCODE
Identifier
1
AL-B-01
2
AL-B-02
3
AL-B-03
4
AL-B-04
5
AL-B-05
6
AL-B-06
7
AL-B-07
8
AL-B-08
9
AL-B-09
10
AL-B-10
11
AL-B-11
12
AL-B-12
13
AL-B-13
14
AL-B-14
15
AL-B-15
16
AL-B-16
17
AL-B-17
18
AL-B-18
19
AL-B-19
20
AL-B-20
21
AL-B-21
22
AL-B-22
23
AL-B-23
24
AL-B-24
25
AL-B-25
26
AL-B-26
Type
Size Name
char[3]
4
L1
Description
Al. rpm max
Al. rpm min
Al. Rotation direction
Al. P1 min
Pressure P1 sensor - faulty
Al. P2 max
Pressure P2 sensor - faulty
Al. P3 max
Al. P3 min
Pressure P3 sensor - faulty
Al. T2 max
Temperature T2 sensor - faulty
Al. T3 max
Al. T3 min
Temperature T3 sensor - faulty
Al. T4 max
Al. T4 min
Temperature T4 sensor - faulty
Emercency open
Motor current protection
Fan motor current protection
Oil level drive side
Oil Level gear side
Fault in communication CPU-Display
Motor high temperature
In4 open
Notes
User Password
59
W3-0A5 12-I