maximum speed.
Initial starting torque can be set for each movement by feeding the operator
at full power for 2 seconds, even if operator force control is enabled. Note:
initial starting torque is disabled automatically if the Soft Start function is
enabled.
Important: If the "SPEED" trimmer is adjusted the self-learning
procedure must be repeated because the movement and deceleration
times may change.
DECELERATION:
The operators deceleration function is used on gates to prevent the moving
leaves from slamming at speed into the limit stops at the end of the opening
and closing strokes.
During Operator Time programming (see Main menu) the control unit also
allows programming of deceleration in the desired points (immediately
before full opening and full closing); in addition, using the "DELAY" trimmer
the force intensity can be adjusted during the deceleration phase.
1. OPENING DIRECTION (DIR):
In the default configuration the control unit is set with "OPEN TO RIGHT"
logic (seen from the operator side, with operator installed to the right of
the sliding leaf); if the "OPEN TO LEFT" logic must be enabled (seen from
operator side, operator installed to the left of the sliding leaf), proceed as
follows: use the SELECT key to select the blinking DIR LED and press the
SET key: the OPEN DIRECTION LED will light steady and programming will
be completed. Repeat the procedure if you wish to restore the previous
configuration.
2. STEP-BY-STEP:
In the default configuration the control unit is set with "Automatic" operating
logic enabled (LED n2 off); if the "Step-by-Step" operating logic is required
(LED n2 on), proceed as follows; use the SELECT key to select blinking
LED n2 and then press the SET key: LED n2 becomes steady on and
programming will be completed.
If the "Step-by-Step 1" operating logic is required, repeat the operation
above described, by pressing the SEL key twice instead only one (to obtain
the quick blinking of LED. Repeat the procedure if you wish to restore the
previous configuration.
3. TX CODE: (Remote control code)
Up to 120 remote controls with different codes of either the fixed or the
rolling code type can be saved on the control unit.
Programming:
Programming of the transmission code is performed as follows: use the
SELECT key to select blinking LED L3. Press SET once; the LED will change
its blinking mode (longer 1 0 1 0) to show that the first level is being saved.
On sending the selected code with the desired remote, the CODE LED will
remain steady on to indicate that programming has been completed.
To save the code for pedestrian opening / single leaf proceed as follows:
use the SELECT key to select blinking CODE LED L3. Press SET twice
consecutively; the LED will change its blinking mode (1 1 0 1 1 0) to show
that the pedestrian code is being saved. On sending the selected code
with the desired remote CODE LED L3 will remain steady lit to indicate that
programming has been completed.
If all 120 codes have been saved, repeating the programming operation will
cause all the programming LEDs to start blinking to signal that no further
codes can be saved.
Deletion:
Use SELECT to go to LED L3; activate blinking of the code to be deleted
(CODE or PEDESTRIAN identified by the respective blinking); press and
hold down SET for > 5 s. After this interval the LED will switch off for 2
seconds and the procedure is completed. If all CODE and PEDESTRIAN
codes are deleted, the LED will remain off.
If only PEDESTRIAN codes remain stored, the LED blinking mode will
change (1 1 1 1 0 1 1 1 1 0).
Rule of the first saved Remote control:
When programming remotes the following rule is applied: if the first remote
to be saved is of the rolling code type, the receiver will subsequently
accept only rolling code remotes, thus providing enhanced anti-intrusion
security; if the first remote to be saved is a fixed code type, the receiver will
subsequently accept both fixed code remotes and rolling code remotes,
although only the fixed part of the latter will be controlled (thus effectively
relinquishing the security of the rolling code system).
4. CONDO:
The Condominium function means that during the opening movement or
during the pause time the control unit will not respond to commands sent
16
COMUNELLO ®Copyright 2014 - All right reserved
by Pushbuttons or remotes. In contrast, during the closing movement a
command sent by the Pushbuttons or the remotes will reverse the direction
of movement. This operating mode is invaluable when the automation
includes a loop detector.
In the default configuration the control unit is set with the Condominium
function disabled; if the Condominium function is required, proceed as
follows: use the SELECT key to select blinking LED L4 and then press
the SET key: LED L4 will light steady and programming will be completed.
Repeat the procedure if you wish to restore the previous configuration.
5. MOTOR TIME (Programming of the motor run time of the
operators with max 4 minutes):
The control unit is factory set with preset motor time of 30 seconds
without deceleration. If the motor time of the operators must be changed,
programming must be carried out with the gate closed as follows: use
the SELECT key to select blinking LED L5 and then press the SET key
momentarily; the operator will start the opening movement; when the
desired deceleration starting point is reached press the SET key again; at
the same time the operator will decelerate and reach the desired position;
press SET to terminate the opening cycle. Thereafter LED L5 will start
blinking rapidly; now repeat the motor time and deceleration programming
procedure for the closing cycle. If you do not require the control unit to
perform the deceleration, during programming, when the open-close cycle
has been completed press the SET key twice consecutively rather than
just once.
During programming, instead of the SET key on the control unit you can use
the button on the remote, providing the remote has been saved beforehand.
6. PAUSE TIME: (Programmazione tempo chiusura aut. 4 min. max.):
The control unit is factory set with automatic closing disabled. If you wish
to enable automatic closing proceed as follows: use the SELECT key to
select blinking LED L6 and press the SET key momentarily; now wait for
a time equivalent to the desired time interval; press the SET key again
momentarily and at the same time the automatic closing time will be saved
and LED L6 will remain steady on. If you wish to restore the initial condition
(no automatic closing) select blinking LED L6 and then press the SET key
twice consecutively in a time period of 2 seconds. The LED will switch off
and the operation will be completed.
During programming, instead of the SET key on the control unit you can use
the button on the remote, providing the remote has been saved beforehand.
7. AUTOMATIC PROGRAMMING:
The control unit provides allows Automatic Programming (SIMPLIFIED).
First bring the gate leaves to an intermediate position, use the SELECT
key to select blinking LED L7 and then hold down the SET key; the
control unit executes the Auto programming procedure by performing a
complete opening and closing cycle (keep the SET key pressed until Auto
Programming is completed). During the Auto Programming procedure,
the Deceleration cycle is set automatically at approximately 15% of the
complete cycle.
During Automatic Programming, instead of the SET key on the control unit
you can use the button on the remote, providing the remote has been
saved beforehand.
EXTENDED MENU 1
The control unit is factory set to allow direct selection exclusively of the main
menu functions. If you wish to enable the functions described in Extended
Menu 1, proceed as follows: select blinking LEV LED and press SET once.
The LED will start blinking. This means there will be 30 seconds to select
the functions of Extended Menu 1 using the SELECT and SET keys; once
an additional 30 seconds have elapsed the control unit reverts to the main
menu.
L1
FOTOTEST
L2
PEDESTRIAN TIME
L3
DECELERATION
L4
REMOTE CODE PGM
L5
RELEASE STROKE
L6
SLAM LOCK
L7
COURTESY LIGHT
LEV LEV
1. PHOTOCELLS TEST:
The control unit is factory set with the photocells test disabled; proceed
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 FLASH