Durchgangsprüfung
10
1.
continuity check
A measured value of < 50 ohms is recognised as continuity; this is confirmed by an audible signal.
If „O.L." appears on the display instead of a measured value, either the measuring range has been
exceeded or the measuring circuit is not closed or has been interrupted.
!
During the continuity check, the components must be de-energized.
AC/DC voltage measurements
11
1.
AC/DC
AC/DC
mV
Voltage detection, non-contact (AC warning)
12
The non-contact voltage detector integrated in the meter is able
to detect AC voltages from 100 V to 600 V. Switch the device
on and run the voltage sensor along the object to be tested
(5 - 10 mm). The display (15) lights up if AC voltage is detected.
Non-contact voltage detection is not a substitute for
!
conventional two-pole voltage testing. As the device
detects an electrical field, it will react even to static charge.
!
The detector is inoperative when auto power-off switches off the measuring device or when
the function selector switch is set to the OFF position.
22
EN
2.
3.
Ω, diode check
and continuity
check selection
2.
AC/DC
V
selection
Black
Red
3.
Black
Connect the measuring contacts
to the object to be tested
Black
Red
Red