PHE 75/PHE 80
LEAKAGE TEST
Gas connections on the heater are leak tested at the factory prior to shipment. A complete gas tightness
check must be performed at the installation site due to possible mishandling in shipment or excessive
pressure being applied to the heater.
Make a soap solution of one part liquid detergent and one part water. The soap solution can be applied
with a spray bottle, brush or rag. Soap bubbles will appear in case of a leak.
The heater must be checked with a full cylinder.
Make sure the safety control valve is in the OFF position.
Turn the gas supply ON.
In case of a leak, turn off the gas supply. Tighten any leaking fittings, then turn the gas supply on and
recheck.
Never leak test while smoking.
OPERATION AND STORAGE
TO TURN ON THE HEATER
1. Turn on the valve on the gas supply cylinder completely.
2. Press and turn the variable control knob to PILOT position (counter-clockwise 90º).
3. Press down the variable control knob and hold for 30 seconds. While holding down the variable control
knob, press the igniter button several times until the pilot flame lights. Release the variable control knob
after the pilot flame lights.
Note:
If a new tank has just been connected, please allow at least one minute for the air in the gas pipeline to
purge out through the pilot hole.
When lighting the pilot flame make sure that the variable control knob is continuously pressed down while
pressing the igniter button. Variable control knob can be released after the pilot flame lights.
If the pilot flame does not light or it goes out, repeat step 3.
4. After the pilot flame lights, turn the variable control knob to maximum position and leave it there for 5
minutes or more before turning the knob to desired temperature position.
Warning: check that no broken on the glass is found before operation
TO TURN OFF THE HEATER
1.Turn the variable control knob to PILOT position.
2.Press and turn the variable control knob to OFF position
Igniter
Variable control knob
3.Turn off the valve on the gas supply cylinder completely
Off: the heater stop work
Hi: maximum temperature
position
Lo: minimum temperature
position
24