Electric Connections - Aprimatic Flexi 300EL Manual De Instrucciones

Central de comando para 2 motores 24vdc
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2A - CABLES SECTION
- The control unit must be powered (by its external fuse box terminal), through a cable which must be at least 3x1.5 mm² wide. If
the distance between the control unit and the grounding system is more than 30m it is necessary to install an electric discharger
near to the control unit.
- The cables which will be used for the low-tension must be at least 0.25 mm² wide.
- If the length between the control unit and the grounding system is more than 30 m, it is necessary to use screen cables. If the
distance increases, it is necessary to increase also the section of the wires, to avoid current loss.
- Do not link the cables in underground box, or in inside the pipes.
- Use only RG58 wires to connect external antennas (it can be provided as accessory with included power cables).
2B - CONNECTION DRAWING
POWER SUPPLY
230 VAC
CLOSING PHOTOCELL
CONNECTION
+
-
RX
TX
NC
C
NO
19 18 16
TERMINAL 2 IS THE COMMON FOR THE CONNECTION OF THE MECHANICAL RIB
ANTENNA
(See paragraph 12B)
LIMIT SWITCH
5. Terminals 3,4,6,7 common (limit switches)
(see notes
below)
FLASHING LAMP
(See paragraph 12A)
9. FLASHING LAMP + (+24 Vdc max 15W)
ELECTRIC LOCK
(See paragraph 12D)
COMMANDS
(See paragraph 10)
16. Safety devices in closing contact PHO1
PHOTOCELLS
17. Safety devices in opening contact PHO2
WARNING LIGHT
18. Terminals 19 and 20 COMMON (0V)
(See paragraphs
11 – 12c)
20. + WARNING LIGHT (12Vdc max 3W)
PLEASE NOTE:
- Every contact which will be connected to the control unit must be free contact.
- The limit switches (terminals 3,4,5,6,7), if not used, have to be free (not bridged). The control unit activate the contact only if it receive signals
from connected contacts.
- If there are no connected devices on the terminal 16 (normally closed input "PHO1"), terminal 17 (normally closed input "PHO2") and/or terminal
14 ("STOP"), the concerning inputs must be bridged.
- If there are connected devices on the terminal 16 (normally closed input "PHO1"), terminal 17 (normally closed input "PHO2") and/or terminal 14
("STOP"), the concerning inputs must not be bridged.
- If the first wing beat on the other one, "MOT1" (terminal 24,25) must start first. Then, it will be necessary to regulate the delay between the
wings through the trimmer "DEL" (see paragraph 4B).
- If there is only 1 motor connected, it must be connected on "MOT1" (terminals 24,25), and the "DEL" trimmer (paragraph 4B) must be set at
minimum.
- If there are more than 1 device connected to the normally closed input "PHO1" (terminal 16), "PHO2" (terminal 17) and "STOP" (terminal 14),
they must be connected in series (see paragraphs 10C, 11A and 11B).
- If there are more than 1 device connected to the normally open input "STR" (terminal 12) and "PED" (terminal 15), they must be connected in
parallel (see paragraphs 10A and 10B).
- If an external antenna is connected, the built-in wire in the terminal 1 must be removed.

2 - ELECTRIC CONNECTIONS

FUSE 3.15A
OPENING PHOTOCELL
CONNECTION
+ -
+
-
RX
NC
C
NO
19 18
19 18 17
1. ANTENNA signal
2. ANTENNA sock
3. Opening limit switch – motor 1
4. Closing limit switch – motor 1
6. Opening limit switch – motor 2
7. Closing limit switch – motor 2
8. FLASHING LAMP negative (0 V)
10. Electric lock control consent
11. Electric lock control negative
12. START contact
13. Terminal 12 – 14 – 15 COMMON
14. STOP contact
15. Pedestrian opening contact PED
19. + PHOTOCELLS (12Vdc)
21. 22.23. TRANSFORMER
24. 25. MOTOR 1
26. 27. MOTOR 2
+ -
TX
19 18
MOT2
MOT1
ANT
GND
FOP1
FCC1
0V
FOP2
RADIO RECEIVER
FCC2
DIRECTION
LAMP
+V
LOW
TENSION
ELET
FUSE
0V
START
0V
STOP
PED
PHO1
PHO2
0V
+VA
+TX
2A
2A
MEMORY
CARD
DIRECTION

Publicidad

Tabla de contenido
loading

Tabla de contenido