Resetting the time and date

Note: The time and date are set in the factory. Should the batteries be flat for
an extended period (nothing in the display) or if it has taken too long to
change the batteries, you will need to reset the time and date.
1. Hold the
button down for 2 seconds.
PROG
2. With the handwheel select the year.
3. Press the
button to confirm.
PROG
4. Repeat steps 2-3 to set the month, day, hour and minute.
Emergency mode (adjusting the valve when the batteries are
empty)
1. Remove the control unit.
2. Operate the heating valve by hand using the handwheel on the valve
actuator: + warm / – cold (see Fig. G).

Carrying out manual adaption

Manual adaption is required when the radiator does not become cold in the
position
or error messages
or
appear in the display (see: Help
with problems).
1. Remove the control unit.
2. Turn the handwheel on the valve actuator clockwise until the valve is
closed.
3. Hold the
button down.
4. Slide the control unit onto the valve actuator as far as the stop and latch it.
Manu
Manu
The display changes from
to
.
The manual adaption is completed.