Fallo De Interruptor - GE UR Serie Manual De Instrucciones

Tabla de contenido

Publicidad

5.5 ELEMENTOS AGRUPADOS
RUTA: SETTINGS [AJUSTES]
BREAKER FAILURE 1(24) [FALLO DE INTERRUPTOR 1(24)]
BREAKER FAILURE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
5
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
5-62
GROUPED ELEMENTS [ELEMENTOS AGRUPADOS]
BREAKER FAILURE
CURRENT SUPV 1
BF1 CURRENT SUPV
FUNCTION: Disabled
BF1 CT:
F1
BF1 AMP SUPV
PICKUP: 1,050 pu
BF1 AMP HISET
PICKUP: 1,050 pu
BF1 AMP LOSET
PICKUP: 1,050 pu
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
BF1 INITIATE:
Off
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 AMP SUPV OP A:
Off
BF1 AMP SUPV OP B:
Off
BF1 AMP SUPV OP C:
Off
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
Relé diferencial de barras B90

5.5.4 FALLO DE INTERRUPTOR

SETTING GROUP 1(6) [GRUPO DE AJUSTES]
Rango: Disabled (desactivado), Enabled (activado)
Rango: canales de intensidad disponibles
Rango: 0,000 a 30,000 pu en escalones de 0,001
Rango: 0,000 a 30,000 pu en escalones de 0,001
Rango: 0,000 a 30,000 pu en escalones de 0,001
Rango: Disabled (desactivado), Enabled (activado)
Rango: operando FlexLogic™
Rango: Yes [Sí], No
Rango: Yes [Sí], No
Rango: operando FlexLogic™
Rango: operando FlexLogic™
Rango: operando FlexLogic™
Rango: Yes [Sí], No
Rango: 0.000 a 65,535 s en escalones de 0,001
Rango: Yes [Sí], No
Rango: 0.000 a 65,535 s en escalones de 0,001
Rango: Yes [Sí], No
5 AJUSTES
GE Multilin

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

B90

Tabla de contenido