MAINTENANCE
8.1
Periodic maintenance
1.
With every periodic inspection, check the float valve
(31) by removing some water from the break tank
(30), or by a short push on the float of the float
valve (31). If necessary clean the inlet filter of the
float valve (31).
2.
Inspect and clean the filter element (24) regularly.
3.
Replace the automatic air vent (8) every two years.
8.2
Replacement parts
The number indications correspond with the main figures
in § 2.1.
Main item
Pump
Cover
Control unit
Cables
Break tank
Automatic air vent
Inlet
23
Spare part
3
Pump, 50Hz
3
Capacitor, 50Hz
3
Seal set
25
Cover S400
5
Control unit Power Box
22
Control unit (HMI)
-
Connector for control unit Power Box
-
WiFi dongle (USB)
-
Fuse set:
-
Solenoid fuse 20x5; 2,5AT (10 pcs)
-
Pump fuse 20x5; 10AT (10 pcs)
-
Mains supply fuse 20x5; 1AM (10 pcs)
-
Cable set - basic cable harness
-
Cable set - additional cable harness refill
30
Break tank assembly
31
Float valve
32
Float switch
8
Automatic air vent
9
Check valve including O-ring, air vent
7
Smart Switch
24
Filter element
23
Inlet flow limiter
21
Pressure sensor
21
Pressure sensor spacer
20
Solenoid valve - internal parts
20
Solenoid valve - coil
4.
Replace the interior of the solenoid valve (22) every
year.
5.
Always fix the vapor-tight insulation after
maintenance.
NOTE
Proper and regular maintenance will
•
ensure correct functioning of the unit
and maximize the life time expectancy
as well as a trouble free operation of the
unit and system.