Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 51
6 STANDARD PROGRAMMING
WARNING For reversible motors with electromagnetic brake, remember to set P062=3.
1 Power Supply
Give power supply, the display shows the following symbols "
*
If the control panel has already been programmed and the power fails or is switched off - once power is returned and a START command
is given, the position reset procedure is performed (see "rESP" in the table "WORKING STATUS MESSAGES" on page 27.
2 Visualisation of inputs and operations-counter status
1. Press the
key for 15 seconds;
2. The display will show respectively:
Inputs status (check it's correct);
Total operations counter (* see P064):
i.g.:
= 3x100* = 3000 operations performed
Maintenance operations-counter (* see P065):
i.g.:
= 5*x500 = 2500 operations remaining
before the maintenance intervention request (
manoeuvres-counter disabled)
3. Hold down the
key to display a cyclic 3 options, or
release the
button to exit the parameter.
3 Selection type of operators
1. Scroll down the parameters with
lise P028;
2. Access the parameter by pressing the
3. Verify that the value corresponds to d007 (GULLIVER), otherwise,
you must select it by pressing
4. Confirm your choice by pressing the
to P028).
4 Selection of direction of motion
1. Scroll down the parameters with
until you visualise P063;
2. Access the parameter by pressing the
3. Acting on
and
- d000=motor in standard position (on the left of
the gap);
- d001=motor in inverted position (on the right of
the gap);
4. Confirm your choice by pressing the
returns again to P063).
Warning: The parameter automatically reverses the
motors output open/close and any limit switch input
open/close.
22

! IMPORTANT !

and
keys until you visua-
key;
and
keys;
key (display returns again
and
keys
key;
keys, set:
key (display
", "
", "
" and then "- - - - ".
=

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido